Rockwell Automation Publication 520-UM001I-EN-E - July 2016 201
Appendix C
RS485 (DSI) Protocol
PowerFlex 520-series drives support the RS485 (DSI) protocol to allow efficient
operation with Rockwell Automation peripherals. In addition, some Modbus
functions are supported to allow simple networking. PowerFlex 520-series drives
can be multi-dropped on an RS485 network using Modbus protocol in RTU
mode.
PowerFlex 520-Series Drive Network
For information regarding EtherNet/IP or other communication protocols, refer
to the appropriate user manual.
Network Wiring
Network wiring consists of a shielded 2-conductor cable that is daisy-chained
from node to node.
Network Wiring Diagram Example
Controller
Esc
Sel
Esc
Sel
Esc
Sel
Esc
Sel
ATTENTION: Never attempt to connect a Power over Ethernet (PoE) cable to the
RS485 port. Doing so may damage the circuitry.
IMPORTANT
The shield is connected at ONLY ONE end of each cable segment.
C1 C2
Master
4
5
TxRxD-
TxRxD+
TxRxD-
TxRxD+
TxRxD-
TxRxD+
Shield Shield Shield
120 ohm resistor
120 ohm resistor
X X X
FRONT
PIN 8PIN 1
TxRxD-
TxRxD+
RS485
(DSI)
AK-U0-RJ45-TB2P
V/T2T/L3S/L2R/L1 U/T1 W/T3
BR+
BR-
DC-
DC+
C1 C2
TxRxD-
TxRxD+
RS485
(DSI)
V/T2T/L3S/L2R/L1 U/T1 W/T3
BR+
BR-
DC-
DC+
PowerFlex 525
Node 1
4
5
PowerFlex 523
Node 2
4
5
PowerFlex 525
Node ā€œnā€

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation B Series and is the answer not in the manual?

Rockwell Automation B Series Specifications

General IconGeneral
BrandRockwell Automation
ModelB Series
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals