Rockwell Automation Publication 520-UM001I-EN-E - July 2016 121
Programming and Parameters Chapter 3
Advanced Program Group (continued)
A456 [PID 1 Trim Hi]
A468 [PID 2 Trim Hi]
PowerFlex 525 only.
Scales the upper value of the trim frequency when trim is active.
Values Default: 60.0 Hz
Min/Max: 0.0/500.0 Hz
Display: 0.1 Hz
PF 525
A457 [PID 1 Trim Lo]
A469 [PID 2 Trim Lo]
PowerFlex 525 only.
Scales the lower value of the trim frequency when trim is active.
Values Default: 0.0 Hz
Min/Max: 0.0/500.0 Hz
Display: 0.1 Hz
PF 525
A458 [PID 1 Trim Sel]
A470 [PID 2 Trim Sel]
PowerFlex 525 only.
Stop drive before changing this parameter.
Sets the PID output as trim to the source reference.
Options 0 “Disabled” (Default) PID Trim is disabled.
1“TrimOn Pot
2 “TrimOn Keypd”
3“TrimOn DSI
4“TrimOn NetOp
5 “TrimOn 0-10V”
6 “TrimOn 4-20”
7“TrimOn Prset
8“TrimOn AnMlt
(1)
9“TrimOn MOP
10 “TrimOn Pulse”
11 “TrimOn Slgic
(1)
12 “TrimOn Encdr”
(1)
13 “TrimOn ENet”
(1)
(1) Setting is specific to PowerFlex 525 drives only.
PF 525

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation B Series and is the answer not in the manual?

Rockwell Automation B Series Specifications

General IconGeneral
BrandRockwell Automation
ModelB Series
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals