48 Rockwell Automation Publication 520-UM001I-EN-E - July 2016
Chapter 1 Installation/Wiring
Typical Multiple Drive Connection Examples
Analog Output
(2)
t088 [Analog Out Sel]
determines analog output
type and drive conditions.
0-10V,
1k Ω minimum
0-20 mA/4-20 mA,
525 Ω maximum
t088
[Analog Out Sel] = 0 through 23
The Analog Output Select jumper must be set to match the analog output signal mode set in
t088
[Analog Out Sel].
(1) Feature is specific to PowerFlex 525 drives only
(2) Feature is not applicable to PowerFlex 523 series A drives.
Input/Output Connection Example
Multiple Digital Input
Connections
Customer Inputs can be
wired per External Supply
(SRC).
When connecting a single input such as Run, Stop, Reverse or Preset Speeds to multiple
drives, it is important to connect I/O Terminal 04 common together for all drives. If they are to
be tied into another common (such as earth ground or separate apparatus ground) only one
point of the daisy chain of I/O Terminal 04 should be connected.
Multiple Analog
Connections
When connecting a single potentiometer to multiple drives it is important to connect I/O
Terminal 14 common together for all drives. I/O Terminal 14 common and I/O Terminal 13
(potentiometer wiper) should be daisy-chained to each drive. All drives must be powered up
for the analog signal to be read correctly.
I/O Connection Example
14
16
Common
+
PowerFlex 523 Series B PowerFlex 525
14
15
Common
+
Customer Inputs Optional Ground Connection
04020402 0402
ATTENTION: I/O Common terminals should not be tied
together when using SNK (Internal Supply) mode. In
SNK mode, if power is removed from one drive,
inadvertent operation of other drives that share the
same I/O Common connection may occur.
Remote Potentiometer Optional Ground Connection
12 13 1413 14 13 14

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation B Series and is the answer not in the manual?

Rockwell Automation B Series Specifications

General IconGeneral
BrandRockwell Automation
ModelB Series
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals