EasyManuals Logo
Home>Samson>Control Unit>2417 Series

Samson 2417 Series User Manual

Samson 2417 Series
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #35 background imageLoading...
Page #35 background image
EB 2517 EN 35
Start-up and operation
6.2 Starting up the plant
Î Start up the regulator after mounting all
parts. Make sure the control line is open
and correctly connected.
Î Open the shut-off valves slowly prefera-
bly starting from the upstream pressure
side. Afterwards, open all the valves on
the consumer side (downstream of the
regulator).
Î Fill the plant slowly with the process me-
dium. Avoid pressure surges.
Î Make sure that the pressure rises simulta-
neously upstream and downstream of the
regulator to avoid damaging the balanc-
ing bellows.
6.2.1 Regulation of liquids
Tostartuptheexcesspressurevalve,open
shut-off valves slowly.
Î Formediumtemperaturesabove150°C,
rstllthecompensationchamberwith
the process medium.
6.2.2 Regulation of steam
Unscrewllerplug(19)onthecompensation
chamber (18). Use the included plastic fun-
nel or a jug to pour in water until it starts to
overow.Screwthellerplugbackinand
tighten it.
Î All pipes conveying the process medium
must be completely drained and dry.
Î Air and condensate must be allowed to
escape from the plant.
Î Allow time for the pipes and valves to
heat up.