Configuration and operation
4.15 STEP 7 configuration of individual parameters
CP 1243-7 LTE
70 Operating Instructions, 01/2015, C79000-G8976-C381-01
4.15.4
Partner stations
4.15.4.1
Partner stations > Telecontrol server
Partner stations > "Telecontrol server"
Partner number
The partner number for the telecontrol server is assigned automatically by the system if
telecontrol communication is enabled.
Station address
The station address of the telecontrol server is assigned automatically by the system if
telecontrol communication is enabled.
Partner stations > "Telecontrol server > "Connection to partner"
Partner IP address
IP address of the telecontrol server
If the CP is connected to a TCSB redundancy group (TCSB V3), here configure the public
IP address of the DSL router via which the telecontrol server can be reached from the
Internet. Set the port forwarding on the DSL router so that the public IP address (external
network) is led to the virtual IP address of the TCSB server PCs (internal network). The
station does not therefore receive any information telling it which of the two computers of
the redundancy group it is connected to.
Connection monitoring
When the function is enabled, the connection to the communications partner (telecontrol
server) is monitored by sending keepalive frames.
The TCP connection monitoring time is set for all TCP connections of the CP in the
parameter group of the Ethernet interface. The setting applies to all TCP connections of
the CP.
Here in the parameter group "Partner stations > Telecontrol server", the globally set TCP
connection monitoring time can be set separately for the telecontrol server. The value set
here overwrites the global value for the telecontrol server that was set in the "Ethernet
interface (X1) > Advanced options > TCP connection monitoring" parameter group.

Table of Contents

Other manuals for Siemens S7-1200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens S7-1200 and is the answer not in the manual?

Siemens S7-1200 Specifications

General IconGeneral
Digital InputsIntegrated in CPU or via signal modules (SM)
Digital OutputsIntegrated in CPU or via signal modules (SM)
Analog InputsIntegrated in CPU or via signal modules (SM)
Analog OutputsIntegrated in CPU or via signal modules (SM)
CommunicationPROFINET
Communication Ports1 x PROFINET
I/O ModulesSignal Modules (SM)
ProgrammingSTEP 7
Power Supply24V DC
Operating Temperature0°C to 55°C
Expansion ModulesCommunication Modules (CM), Battery Modules (BM)

Related product manuals