Configuration and operation
4.16 Access to the Web server
CP 1243-7 LTE
Operating Instructions, 01/2015, C79000-G8976-C381-01
89
Status
Meaning
8502 Syntax error. Check the following configuration data:
Message configuration > Message parameters:
Email address (sender)
8535 SMTP authentication incomplete. Check the "User name" and "Password" parameters in
the CP configuration.
8550 SMTP server cannot be reached. You have no access rights. Check the following configu-
ration data:
CP configuration > E-mail configuration:
User name
Password
Email address (sender)
Message configuration > Message parameters:
Recipient address ("To" or "Cc").
8554
Transfer failed
85xx Other error message from the e-mail server
Apart from the leading "8", the status corresponds to the three-digit error number of the
SMTP protocol.
Include value
If you enable the option "Include value", the CP sends a value for the placeholder $$ from
the memory area of the CPU in the message. To do this, you configure a PLC tag whose
value is integrated in the message.
The value is entered in the message text instead of the placeholder $$.
4.16
Access to the Web server
Access to the Web server of the CPU
The Web server of the S7-1200 station is located in the CPU. Via the LAN interface of the
CP, you have access to the Web server of the CPU.
Access using HTTPS: When there is secure access (HTTPS) to the Web server using the IP
address of the CP, the SSL certificate of the CPU is displayed.

Table of Contents

Other manuals for Siemens S7-1200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens S7-1200 and is the answer not in the manual?

Siemens S7-1200 Specifications

General IconGeneral
Digital InputsIntegrated in CPU or via signal modules (SM)
Digital OutputsIntegrated in CPU or via signal modules (SM)
Analog InputsIntegrated in CPU or via signal modules (SM)
Analog OutputsIntegrated in CPU or via signal modules (SM)
CommunicationPROFINET
Communication Ports1 x PROFINET
I/O ModulesSignal Modules (SM)
ProgrammingSTEP 7
Power Supply24V DC
Operating Temperature0°C to 55°C
Expansion ModulesCommunication Modules (CM), Battery Modules (BM)

Related product manuals