'NETWORK' LED
PLC tag (data type UInt) for the status of the connection for the data service in the mobile
wireless network.
Date of last successful logon to network
PLC tag (data type DTL) for the date on which the CP last logged in to the mobile
wireless network.
Date of last unsuccessful logon to network
PLC tag (data type DTL) for the date on which the CP was last unable to log in to the
mobile wireless network.
Date of last successful logon to TCSB
PLC tag (data type DTL) for the date on which the CP last logged in to the telecontrol
server.
Date of last unsuccessful logon to TCSB
PLC tag (data type DTL) for the date on which the CP was last unable to log in to the
telecontrol server.
4.15.6
E-mail configuration
Configuring e-mails in STEP 7
In the "E-mail configuration" entry, you configure the protocol to be used and the data for
access to the e-mail server in STEP 7.
In the message editor ("Messages" entry in STEP 7), you configure the individual e-mails,
see section Messages (Page 86).
E-mail configuration
With the default setting of the SMTP port 25, the CP transfers unencrypted e-mails.
If your e-mail service provider only supports encrypted transfer, use one of the following
options:
Port no. 587
By using STARTTLS, the CP sends encrypted e-mails to the SMTP server of your e-mail
service provider.
Recommendation: If your e-mail provider offers both options (STARTTLS / SSL/TLS), you
should use STARTTLS with port 587.
Port no. 465
By using SSL/TLS (SMTPS), the CP sends encrypted e-mails to the SMTP server of your
e-mail service provider.
Ask your e.mail service provider which option is supported.

Table of Contents

Other manuals for Siemens S7-1200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens S7-1200 and is the answer not in the manual?

Siemens S7-1200 Specifications

General IconGeneral
Digital InputsIntegrated in CPU or via signal modules (SM)
Digital OutputsIntegrated in CPU or via signal modules (SM)
Analog InputsIntegrated in CPU or via signal modules (SM)
Analog OutputsIntegrated in CPU or via signal modules (SM)
CommunicationPROFINET
Communication Ports1 x PROFINET
I/O ModulesSignal Modules (SM)
ProgrammingSTEP 7
Power Supply24V DC
Operating Temperature0°C to 55°C
Expansion ModulesCommunication Modules (CM), Battery Modules (BM)

Related product manuals