Siemens Building Technologies Commissioning Guide CM1G5192en
HVAC Products 6 Commissioning 26.02.2003
6.2 Checklist prior to startup
Checkpoints
ü
üü
ü
Is the output of the VSD ≥ motor rating?
Is the operating voltage range ok?
Is the rated voltage of the SED2 greater than the motor rated voltage?
Is the cross-section of the mains cable correct?
Are the cross-section and the length of the motor cables correct, and are
they connected properly?
Are all control lines connected properly?
Is the motor not blocked mechanically?
Is the medium (water) available for the pump (no dry run!)
Is there no pumping or blowing against still open valves or dampers?
Is the danger zone free of items or personnel?