09.02 Start-Up
Siemens AG 6SE7087-6AK85-1AA0
4-19
Rectifier/Regenerating Unit Operating Instructions
Bit 3: Run enable command (H "Run enable")
The RUN ENABLE command (firing pulse enable) is implemented with an H signal.
After the command has been accepted:
If the READY status (011) still applies.
Changeover to the RUN status (014); the firing pulses are enabled and the voltage setpoint is approached
over the pre-charging ramp.
Bit 3: Run inhibit command (L "Run inhibit")
The RUN INHIBIT command (firing pulses disabled) is implemented with an L signal.
After the command has been accepted:
If the RUN status (014) applies:
Changeover to the READY status (01); the firing pulses are inhibited.
Bit 4 to 6: reserved
Bit 7: Acknowledge command ( "Acknowledge")
The command is executed with a positive edge change from L to H (L H) only in the FAULT status (007).
After the command has been accepted:
All actual faults are deleted after having been previously transferred into the diagnostics memory
If no faults are present:
The drive changes into the status SWITCH-ON INHIBIT (008)
If actual faults are present:
The drive remains in the FAULT status (007).
NOTE
The acknowledge command is simultaneously effective from three sources (P565, P566 and P567) and
always from the PMU!
Bit 8: Inching 1 ON command ( "Inching 1 ON")
The command is executed with a positive edge change from L to H (L H) only in the READY-TO-SWITCH-
ON status (009).
After the command has been accepted
an ON command is automatically executed (description, refer to control word bit 0).
Bit 8: Inching 1 OFF command (L "Inching 1 OFF")
The command is executed with an L signal.
After the command has been accepted:
An OFF 1 command is automatically executed (description, refer to control word bit 0).
Bit 9: Inching 2 ON command ( "Inching 2 ON")
The command is executed with a positive edge change from L to H (L H) only in the READY-TO-SWITCH-
ON status (009).
After the command has been accepted
an ON command is automatically executed (description, refer to control word bit 0).
https://www.aotewell.com
AoteWell Automation Sales Team
Sales@aotewell.com
AoteWell LTD
Buy Siemens PLC HMI Drives at AoteWell.com
https://www.aotewell.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Simovert 6SE70 Series and is the answer not in the manual?

Siemens Simovert 6SE70 Series Specifications

General IconGeneral
BrandSiemens
ModelSimovert 6SE70 Series
CategoryDC Drives
LanguageEnglish

Related product manuals