Parameter List 09.02
5-8 Siemens AG 6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit Operating Instructions
PNU
*
: Conf.
Par.
OP1S parameter name
Description
Value range
[phys. unit]
Selection text
Display
Indies
Factory-
setting
See
Modify
(access /
status
5.4 Drive data
P070
*
MLFB(6SE70 ... )
MLFB (order number) of the rectifier/regenerating unit
On POWER ON, the "Bootstrap" function is automatically selected as
long as P070 has not been set!
Enter the code of the corresponding MLFB here (see Section 4.3.9.2)
PNU=46Hex; Type=O2; Scaling: 1Hex
=
1
0 to 120 -
Depends on
unit
3/U BR
3/U
P071
*
Line Volts
Line voltage of the rectifier bridge
RMS value of the rated voltage at which the power section is actually
operated
PNU=47Hex; Type=O2; Scaling: 1Hex
=
1
100 to 1000
[V]
-
acc. to P070
2/ ABR
2/ A
P074 Limit LowVoltage
Response threshold for undervoltage disconnection and phase failure
monitoring and threshold for DC link voltage (ssee Section 4.3.10.1).
PNU=4AHex; Type=O2; Scaling: 1Hex
=
1
10 to 100
[% of P071]
or
[% of 1.35
*
P071]
-
61
2/ BR
2/ BR
P075
*
Rtd Amps
Rated DC voltage of the R/R unit
Output DC current (average value) at the power terminals X1-C and X1-D.
PNU=4BHex; Type=O2; Scaling: 1Hex
=
0.1
0.0 to 3276.7
[A]
-
acc. to P070
2/U BR
2/U
P076
*
Config. PCircuit
Configuration of the power section
xx1 Motoring only
xx2 Motoring and generating possible
00x No
parallel power section connected
x1x to x2x Number of additional
parallel-connected power sections in
feed direction
0xx to 2xx Number of additional
parallel-connected power sections in
recovery direction
The number of parallel feed power sections must be greater than or equal to
the number of parallel recovery power sections:
Permitted configurations: P076= 00x, 01x, 02x, 11x, 12x, 22x
Feed power section(s): E EE EEE EE EEE EEE
Recovery power section(s): R R R RR RR RRR
Correction factor: 1 2 3 1 3/2 1
In recovery direction, calculation of the effective U
d
controller gain and
determination of the effective DC link capacitance for the load current
calculation take the above correction factor into account.
PNU=4CHex; Type=L2; Scaling: 1Hex
=
1
001 to 222 -
002
3/ ABR
3/ A
https://www.aotewell.com
AoteWell Automation Sales Team
Sales@aotewell.com
AoteWell LTD
Buy Siemens PLC HMI Drives at AoteWell.com
https://www.aotewell.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Simovert 6SE70 Series and is the answer not in the manual?

Siemens Simovert 6SE70 Series Specifications

General IconGeneral
BrandSiemens
ModelSimovert 6SE70 Series
CategoryDC Drives
LanguageEnglish

Related product manuals