09.02 Parameter List
Siemens AG 6SE7087-6AK85-1AA0
5-3
Rectifier/Regenerating Unit Operating Instructions
PNU
*
: Conf.
Par.
OP1S parameter name
Description
Value range
[phys. unit]
Selection text
Display
Indices
Factory-
setting
See
Modify
(access /
status)
5.1 Operation display
r000 Operation Display
Status display, faults and warnings of the S/F unit
For description, see Chapter 6 Operator control
o
014 Run
- - No thyristor bridge in circuit
I Rectifier bridge in circuit
II Regenerative bridge in circuit
o
012 Test phase
Wait until the thyristor test and/or earth-fault test has been
completed (Selection function: P3530 and/or P3540).
Note: The thyristor test can only be conducted if the DC link
voltage is less than 5% of 1.35
*
P071. Following an ON
command, therefore, wait in operating status
o
012 until this
condition is satisfied!
o
011 Wait for Run enable
Wait for Run enable
o
010 Wait for system voltage
Wait until the system voltage has been checked.
or Wait for voltage at power terminals X1-U1, X1-V1, X1-W1
(rectifier bridge)
or Wait for voltage at power terminals X4-1U2, X4-1V2, X4-1W2
(regenerative bridge)
or Wait for checkback signal "System contactor energized"
or Waiting state before energizing the system contactor (Waiting
time P409)
o
009 Wait for Ready to Switch On
Wait for Ready to Switch On (OFF1 active)
or Wait until internal OFF state is canceled by an external OFF
command.
o
008 Switch-on inhibit; isolation (OFF2)
Wait for acknowledgment of switch-on inhibit by activating the
SWITCH-OFF command
or Isolation implemented (OFF2)
or Wait until a valid USS telegram to SST1 has been received
(only if P687 is set to 0)
or Wait until a valid peer-to-peer telegram to SST2 has been
received (only for P688=1, when P687.i003 is set to 0)
o
007 Fault
A fault message has been received.
o
021 Download
A parameter download over SST1 can be executed
o
005 Drive settings
o
004 Hardware settings
o
002 Electronics initialization
The option module electronics are initialized
or The basic unit electronics are initialized
o
001 Establish factory setting
o
000 Set MLFB
PNU=00Hex; Type=O2; Scaling: 1Hex
=
1
0 to 21 -
-
1/UHABR
https://www.aotewell.com
AoteWell Automation Sales Team
Sales@aotewell.com
AoteWell LTD
Buy Siemens PLC HMI Drives at AoteWell.com
https://www.aotewell.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Simovert 6SE70 Series and is the answer not in the manual?

Siemens Simovert 6SE70 Series Specifications

General IconGeneral
BrandSiemens
ModelSimovert 6SE70 Series
CategoryDC Drives
LanguageEnglish

Related product manuals