09.02 Parameter List
Siemens AG 6SE7087-6AK85-1AA0
5-3
Rectifier/Regenerating Unit Operating Instructions
PNU
*
: Conf.
Par.
OP1S parameter name
Description
Value range
[phys. unit]
Selection text
Display
Indices
Factory-
setting
See
Modify
(access /
status)
5.1 Operation display
r000 Operation Display
Status display, faults and warnings of the S/F unit
For description, see Chapter 6 Operator control
o
014 Run
- - No thyristor bridge in circuit
I Rectifier bridge in circuit
II Regenerative bridge in circuit
o
012 Test phase
Wait until the thyristor test and/or earth-fault test has been
completed (Selection function: P353≠0 and/or P354≠0).
Note: The thyristor test can only be conducted if the DC link
voltage is less than 5% of 1.35
*
P071. Following an ON
command, therefore, wait in operating status
o
012 until this
condition is satisfied!
o
011 Wait for Run enable
Wait for Run enable
o
010 Wait for system voltage
Wait until the system voltage has been checked.
or Wait for voltage at power terminals X1-U1, X1-V1, X1-W1
(rectifier bridge)
or Wait for voltage at power terminals X4-1U2, X4-1V2, X4-1W2
(regenerative bridge)
or Wait for checkback signal "System contactor energized"
or Waiting state before energizing the system contactor (Waiting
time P409)
o
009 Wait for Ready to Switch On
Wait for Ready to Switch On (OFF1 active)
or Wait until internal OFF state is canceled by an external OFF
command.
o
008 Switch-on inhibit; isolation (OFF2)
Wait for acknowledgment of switch-on inhibit by activating the
SWITCH-OFF command
or Isolation implemented (OFF2)
or Wait until a valid USS telegram to SST1 has been received
(only if P687 is set to ≠0)
or Wait until a valid peer-to-peer telegram to SST2 has been
received (only for P688=1, when P687.i003 is set to ≠0)
o
007 Fault
A fault message has been received.
o
021 Download
A parameter download over SST1 can be executed
o
005 Drive settings
o
004 Hardware settings
o
002 Electronics initialization
The option module electronics are initialized
or The basic unit electronics are initialized
o
001 Establish factory setting
o
000 Set MLFB
PNU=00Hex; Type=O2; Scaling: 1Hex
=
∧
1
0 to 21 -
-
1/UHABR