Parameter List 09.02
5-18 Siemens AG 6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit Operating Instructions
PNU
*
: Conf.
Par.
OP1S parameter name
Description
Value range
[phys. unit]
Selection text
Display
Indices
Factory-
setting
See
Modify
(access /
status)
5.10 Control and status word
r550 Control Word 1
Display of the control word 1 bits 0 to 15, see Section 4.3.1.1.2
6
7
14
15
2
3
10
11
0
1
8
9
4
5
12
13
PNU=226Hex; Type=V2; Scaling: 1Hex
=
∧
1
- 2/ BR
r551 Control Word 2
Display of the control word 2 bits 16 to 31, see Section 4.3.1.1.2
22
23
30
31
18
19
26
27
16
17
24
25
20
21
28
29
PNU=227Hex; Type=V2; Scaling: 1Hex
=
∧
1
- 2/ BR
r552 Status Word 1
Display of the status word 1 bits 0 to 15, see Section 4.3.1.2.2
6
7
14
15
2
3
10
11
0
1
8
9
4
5
12
13
PNU=228Hex; Type=V2; Scaling: 1Hex
=
∧
1
- 2/ BR
r553 Status Word 2
Display of the status word 2 bits 16 to 31, see Section 4.3.1.2.2
22
23
30
31
18
19
26
27
16
17
24
25
20
21
28
29
PNU=229Hex; Type=V2; Scaling: 1Hex
=
∧
1
- 2/ BR
P554
*
Src ON/OFF1
Source of the 'ON/OFF1' command (control word 1, bit 0)
0: OFF1
1: Not allowed
1001: CUR, binary input 1
1010: PMU ON/OFF keys
Other values: see allowed settings in Section 4.3.1.1 (process data
wiring of the control word)
B/R Parameter
PNU=22AHex; Type=L2; Scaling: 1Hex
=
∧
1
0 to 6005 2
(i001=1010)
(i002=1001)
2/ BR
2/ BR
P555
*
Src1 OFF2
Source 1 of the 'OFF2' command (control word 1, bit 1)
0: Not allowed
1: Condition for operation
1002: binary input 2 of the CUR board
Other values: see allowed settings in Section 4.3.1.1 (process data
wiring of the control word)
B/R Parameter
PNU=22BHex; Type=L2; Scaling: 1Hex
=
∧
1
1 to 6005 2
(i001=1010)
(i002=1002)
2/ BR
2/ BR