Start-Up 09.02
4-28 Siemens AG 6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit Operating Instructions
4.3.1.3 Setpoints
The only possible setpoint selection that can be programmed on a rectifier/regenerating unit is the selection of
the Id setpoint for a rectifier/regenerating unit in slave mode (e.g. the slave rectifier/regenerating unit in 12-pulse
operation) using parameter
(See also Chapter 5 "Parameter list")
The control word command can be used for effecting the changeover:
"Basic and reserve settings"
See Section 4.4 "Function diagrams"
The source for the setpoint is defined using values:
Value entry in
Index1 i001 active when "basic setting" selected" (control word)
Index2 i002 active when "reserve setting" selected (control word)
Value assignment for
P486 "Source Id-setpoint":
Value Source
0000 Constant setpoint = 0
Factory setting: P486 i001, i002
2002 SST1 (PMU -X300 or -X100:1...5) Word2
2003 Word3
2004 Word4
only if word 4 is not assigned for "control
word 2 with 2004 (Section 4.3.1.1)
... consecutively to
2016 Word16
OPTIONS
3002 CB/TB Word2
3003 Word3
3004 Word4
only if word 4 is not assigned for "control
word 2 with 3004 (Section 4.3.1.1)
... consecutively to
3016 Word16)
4101 SCB1 with SCI 1,Slave1, analog input AE1
4102 AE2
4103 AE3
4201 SCB1 with SCI 1,Slave2, analog input AE1
4202 AE2
4203 AE3
4501 SCB-SST (only Peer to Peer, Word1)
only if word 1 is not assigned for "control
word 1 with 4501 (Section 4.3.1.1)
4502 USS /Peer to Peer, Word2
4503 USS /Peer to Peer, Word3
4504 USS /Peer to Peer, Word4
only if word 4 is not assigned for "control
word 2 with 4504 (Section 4.3.1.1)
4505 USS /Peer to Peer, Word5
4506 only USS, Word6
... consecutively to
4516 only USS, Word6
6002 SST2 (PTP1, A2-X117:1..5) Peer-to-Peer, Word2
6003 SST2 (PTP1, A2-X117:1..5) Peer-to-Peer, Word3
6004 SST2 (PTP1, A2-X117:1..5) Peer-to-Peer, Word4
6005 SST2 (PTP1, A2-X117:1..5) Peer-to-Peer, Word5
https://www.aotewell.com
AoteWell Automation Sales Team
Sales@aotewell.com
AoteWell LTD
Buy Siemens PLC HMI Drives at AoteWell.com
https://www.aotewell.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Simovert 6SE70 Series and is the answer not in the manual?

Siemens Simovert 6SE70 Series Specifications

General IconGeneral
BrandSiemens
ModelSimovert 6SE70 Series
CategoryDC Drives
LanguageEnglish

Related product manuals