09.02 Start-Up
Siemens AG 6SE7087-6AK85-1AA0
4-7
Rectifier/Regenerating Unit Operating Instructions
4.2.3 Parameterization for "Expert application"
Parameterization can be simplified by selecting an appropriate factory setting via parameter P077 using special
functions such as 12-pulse mode with two rectifier/regenerating units coupled via a peer-to-peer link. In this
case, this is carried out by selecting the function "Generate factory setting" as described in Section 4.3.9.1 with
P0770. Then the parameterization shown in the following diagram can be carried out.
In all other cases, the following parameterization is started immediately.
P161 =
P160 =
P071 =
P051 = 3
P052 = 5
P050 =
P555 = 2001
P554 = 2001
P053 =
P076 =
Commands
via OP1S?
yes
no
Language (only important when an OP1S is in use; see Section 9.4):
0: German, 1: English, 2: Spanish, 3: French, 4: Italian
Access stage "Standard mode“
Parameterization enable
e.g. with P053=6, the parameters from the parameterization unit (PMU)
and from serial interface 1 of the basic unit (SST1- and therefore also
from the optional user-friendly operator panel OP1S) can be modified.
Operator control
If the unit is to be switched on and off via the optional user-friendly
operator panel OP1S:
P554=2001 Source for control command "ON/OFF1"
P555=2001 Source for control command "OFF2"
Drive setting
Supply voltage [V
Value of the rated voltage at the rectifier bridge
Configuration of the power section
P076 = 00x No power section connected in parallel
11x 1 rectifier/regenerating parallel unit connected in parallel
with the basic unit
01x 1 common rectifier parallel unit connected in parallel with
the basic unit
etc.
22x 2 rectifier/regenerating parallel units connected in
parallel with the basic device
(see also Chapter 5, P076 and Chapter 3.7)
Current limits:
P160 = Max. supply current (in % P075 rated current of
rectifier/regenerating unit (factory setting: +150% only briefly
available)
P161 = Max. regenerative current (in % of P075 rated current of
rectifier/regenerating unit (factory setting: -150% only briefly
available)
https://www.aotewell.com
AoteWell Automation Sales Team
Sales@aotewell.com
AoteWell LTD
Buy Siemens PLC HMI Drives at AoteWell.com
https://www.aotewell.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Simovert 6SE70 Series and is the answer not in the manual?

Siemens Simovert 6SE70 Series Specifications

General IconGeneral
BrandSiemens
ModelSimovert 6SE70 Series
CategoryDC Drives
LanguageEnglish

Related product manuals