Start-Up 09.02
4-22 Siemens AG 6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit Operating Instructions
Bits 20 to 22: reserved
Bit 23: 12-pulse mode selection command (H "12-pulse mode is selected")
The command is executed with an H signal and causes a change in operational behavior from that of a single
unit (i.e. a "normal" single unit becomes a 12-pulse master or a 12-pulse slave depending on parameter P587
or control word bit 27). See Section 3.8.4 for further details.
Bits 24 and 25: reserved
Bit 26: Fault, external 2 command (L "Fault, external 2")
The command is recognized with an L signal and does not become active until the pre-charging time (P329)
and an additional time delay of 3000 ms has elapsed when the operating mode RUN is active. During formation
(P052=20) or circuit identification (P052=21), the command is ineffective.
After the command has been accepted
Changeover to the FAULT status (007) (fault F036)
The firing pulses are inhibited and the main contactor, if installed, drops out (see also Chapter 7 "Faults and
Warnings").
Bit 27: Master/slave changeover (H "Slave S/F unit"/L "Master S/F unit")
The command switches between slave and master mode.
Slave S/F unit: The closed-loop control operates with an external DC link current setpoint
Even when a thyristor test is selected (P353=1, 2 or 3) if Ud > 5% it does not
wait in
state
o
012 and the thyristor test is not carried out.
Master S/F unit: The closed-loop control operates with an external DC link current setpoint
Bit 28: Alarm, external 1 command (L "Alarm, external 1")
The command is executed with an L signal.
After the command has been accepted
The operating status is retained. An alarm message (A015) is output (also refer to Section 7 "Fault and
Alarm Messages")
Bit 29: Alarm, external 2 command (L "Alarm, external 2")
The command is executed with an L signal.
After the command has been accepted:
The operating status is retained. An alarm message (A015) is output (also refer to Section 7 " Fault and
Alarm Messages ")
Bit 30: Selection, basic/reserve setting command (L "Basic setting / H "Reserve setting")
The command activates the BASIC SETTING with an L signal and the RESERVE SETTING with an H signal
After the command has been accepted:
The parameter settings of the basic or reserve setting for the control word itself, the setpoint channel, and
the closed-loop control are activated (see "Data sets" in Section 4.1.2 and "Selecting the data sets" in
Section 4.4).
Bit 31: Main contactor checkback signal command (H "Main contactor checkback signal")
This command permits you to include an auxiliary contact of the main contactor in the unit control circuit (an H
signal implies that the main contactor has picked up).
After the command has been accepted:
An operating status >
o
010 is permitted
https://www.aotewell.com
AoteWell Automation Sales Team
Sales@aotewell.com
AoteWell LTD
Buy Siemens PLC HMI Drives at AoteWell.com
https://www.aotewell.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Simovert 6SE70 Series and is the answer not in the manual?

Siemens Simovert 6SE70 Series Specifications

General IconGeneral
BrandSiemens
ModelSimovert 6SE70 Series
CategoryDC Drives
LanguageEnglish

Related product manuals