EasyManuals Logo
Home>Siemens>DC Drives>Simovert 6SE70 Series

Siemens Simovert 6SE70 Series User Manual

Siemens Simovert 6SE70 Series
274 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #115 background imageLoading...
Page #115 background image
09.02 Start-Up
Siemens AG 6SE7087-6AK85-1AA0
4-33
Rectifier/Regenerating Unit Operating Instructions
Example 2: Available: P075 (rated DC current) = 420 A
Required: Map the output current r035 between -630 and +630 A to -10.00 V to
+10.00 A at the analog output
Connect-up parameter r035 at the analog output:
P655 "CUR-AA actual values“ = 035
Convert the required output range in [%]:
r035 should be taken from the parameter list, Section 5:
Analog output: 100% = P075
Thus, the following is obtained for the range to be represented:
-630 A -150% (Parameter value PWE1) represented as V
off1
= -10.00 V
+630 A 150% (Parameter value PWE2) represented as V
off2
= +10.00 V
Define gain factor
P656 and offset P657:
The following is obtained from the formula shown above:
[]
[
]
[
]
(
)
[] []
[]
[]
[]
[]
()
V 0.00 V0.001 V10
% 100
% 150.00- V 6.67
10V
% 100
%PWE Vfactor Gain
V U =V Offset
V6.67
% 300
% 100 V20.00
% 150% 150-
%100 V)10.00 V 10.00(
%PWE %PWE
%100 VU VU
V factor ainG
1
off1
2 1
off2 off1
=+=
×
=
×
=
×
=
×
=
×
=
To be adjusted: Gain
P656 = +6,67 V
offset
P657 = 0,00 V
https://www.aotewell.com
AoteWell Automation Sales Team
Sales@aotewell.com
AoteWell LTD
Buy Siemens PLC HMI Drives at AoteWell.com
https://www.aotewell.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Simovert 6SE70 Series and is the answer not in the manual?

Siemens Simovert 6SE70 Series Specifications

General IconGeneral
BrandSiemens
ModelSimovert 6SE70 Series
CategoryDC Drives
LanguageEnglish

Related product manuals