09.02 Parameter List
Siemens AG 6SE7087-6AK85-1AA0
5-13
Rectifier/Regenerating Unit Operating Instructions
PNU
*
: Conf.
Par.
OP1S parameter name
Description
Value range
[phys. unit]
Selection text
Display
Indices
Factory-
setting
See
Modify
(access /
status)
P316 DC V-Reg +Limit
Positive threshold for the dead band of the setpoint/actual-value difference
of the U
d
controller
A setpoint/actual-value deviation signal for the DC link voltage is not applied
to the U
d
controller until the deviation of the DC link voltage exceeds
the
value set here.
RDS parameter
PNU=13CHex; Type=O2; Scaling: 1Hex
=
0.01
0.00 to 100.00
[%] of 1.35
*
P071
4
0.01
3/ BR
3/ BR
P317 DC V-Reg -Limit
Negative threshold for the dead band of the setpoint/actual-value difference
of the U
d
controller
A setpoint/actual-value deviation signal for the DC link voltage is not applied
to the U
d
controller until the deviation of the DC link voltage drops below
the
value set
RDS parameter
PNU=13DHex; Type=I2; Scaling: 1Hex
=
0.01
-100.00 to 0.00
[%] of 1.35
*
P071
4
-1.00%
3/ BR
3/ BR
P318 DC V(set,red)
DC link voltage setpoint with active DC link reduction (i.e. upon request for
U
d
reduction via control word 1, Bit 11= 1 (control word-source selection via
P571) or for internally generated U
d
reduction command in event of
released current-dependent U
d
reduction (P323= 1))
With parameter setting P318 > 100.00 %, the Ud controller
of the E unit or
the E/R unit can be operated at full signal level
with the recovery direction
blocked (P076= xx1).After precharging, this leads to the control angle α=0.
RDS parameter
PNU=13EHex; Type=O2; Scaling: 1Hex
=
0.01
0.00 to 160.00
[%] of 1.35
*
Supply
voltage at the
rectifier bridge
4
80.00
3/ ABR
3/ ABR
P319 DC V(set,red)Hys
Hysteresis for Ud < Ud(set,red)
(message "Ud reduced")
RDS parameter
PNU=13FHex; Type=O2; Scaling: 1Hex
=
0.01
0.00 to 100.00
[%] of 1.35xP071
4
6.00%
3/ ABR
3/ ABR
P320 Smooth Load Amps
Smoothing time for feedforward load current injection
RDS parameter
PNU=140Hex; Type=O2; Scaling: 1Hex
=
1
0 to 9999
[ms]
4
5
3/ BR
3/ BR
P321 DC CurrThresVred
Current threshold for current-dependent DC link reduction
If I
d
(averaged over 3 current crests) falls below
the value set here, the U
d
setpoint is reduced over a ramp (discharge time P330 active) to the value in
accordance with P318 when current-dependent U
d
reduction (P323=1) is
released.
RDS parameter
PNU=141Hex; Type=O2; Scaling: 1Hex
=
0.01
0.00 to 100.00
[%]
4
30.00
3/ BR
3/ BR
P322 DC CurrHyst.Vred
Hysteresis for current-dependent DC link voltage reduction
If I
d
(averaged over 3 current crests) exceeds
the sum of P321 and the
value set here, the U
d
setpoint increases over a ramp (precharge time P329
active) to the value 1.35
*
U
line,feed
when current-dependent U
d
reduction
is released (P323=1).
RDS parameter
PNU=142Hex; Type=O2; Scaling: 1Hex
=
0.01
0.00 to 100.00
[%]
4
20.00
3/ BR
3/ BR
https://www.aotewell.com
AoteWell Automation Sales Team
Sales@aotewell.com
AoteWell LTD
Buy Siemens PLC HMI Drives at AoteWell.com
https://www.aotewell.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Simovert 6SE70 Series and is the answer not in the manual?

Siemens Simovert 6SE70 Series Specifications

General IconGeneral
BrandSiemens
ModelSimovert 6SE70 Series
CategoryDC Drives
LanguageEnglish

Related product manuals