CAUTION
Direct sunlight
Device damage.
The device can overheat or materials become brittle due to UV exposure.
Protect the device from direct sunlight.
Make sure that the maximum permissible ambient temperature is not exceeded. Refer to
the information in Operating conditions (Page 52).
NOTICE
Mounting location
Ideally, mount device so that face of transducer is at least 300 mm (1 ft) above the highest
anticipated material level.
5.1.1.1 Recommended
Ambient temperature within –40 to +80 °C (–40 to +176 °F)
Process temperature within –40 to +85 °C (–40 to +185 °F)
Environment suitable to the housing rating and materials of construction
Sound path perpendicular to the material surface
Display and local buttons easily accessible for programming
Cable entries easily accessible for wiring
Sufficient room to open device lid with clear access
Mounting surface free from vibration
Place for a laptop computer provided for on-site configuration (optional, as laptop not
required for configuration)
NOTICE
Device rotation
The device can be rotated separate from the process connection.
There is no limit to the number of times device can be rotated without damage.
Installing/mounting
5.1 Basic safety notes
SITRANS Probe LU240 with mA/HART
Compact Operating Instructions, 10/2018, A5E42673704-AB 19

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SITRANS L LU240 and is the answer not in the manual?

Siemens SITRANS L LU240 Specifications

General IconGeneral
BrandSiemens
ModelSITRANS L LU240
CategoryTransmitter
LanguageEnglish

Related product manuals