16
Siemens Building Technologies / HVAC Products CE1B3131x2-en 74 319 0346 0 a 19.11.2004
Do you want to start DHW heating?
(Only with RMH760)
Prerequisites
The heating plant must be commissioned by the heating
engineer.
When the preconditions are met, DHW heating is ready
to be started. Select menu option Preselection and then
choose operating mode
. This is the recom-
mended and energy-saving operating mode.
The following choices are available:
Symbol Operating mode Impact on the DHW circuit? Guide value
Automatic The DHW temperature changes according to the DHW time program,
from normal temperature to reduced temperature, or vice versa
Normal The DHW is maintained at the normal temperature 55 °C
Reduced The DHW is maintained at the reduced temperature 40 °C
Protection No DHW heating: The DHW storage tank remains protected against
frost, however
5 °C
Path:
Main menu > DHW > Operating mode > Preselection