27
Siemens Building Technologies Technologies / HVAC Products CE1B3131x2-en 74 319 0346 0 a 19.11.2004
Info pages boiler sequence manager
(Only with RMK770)
To reach the Info page:
1. Return to the start page by pressing the ESC button.
2. Press the INFO button.
3. Turn the OK knob until the required page appears.
State
On = heat generation on
Off = heat generation off
Cause
Here, the reason for the state of heat generation is
given. It should be considered that the boiler sequence
may be deactivated while the main pump is still running,
e.g. due to frost protection or overtemperature protec-
tion.
Main flow temperature
Actual value below setpoint:
If the actual boiler temperature is lower than the set-
point for a longer period of time, additional boilers will
be released. The time of release depends especially
on the differential of these 2 values.
Actual value above setpoint:
If the actual value remains above the setpoint for a
longer period of time, released boilers will be locked.
Return temperature
This is the temperature of the water returning to the
boiler from the consumers (heating circuit, DHW circuit).

Table of Contents

Other manuals for Siemens Synco 700

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Synco 700 and is the answer not in the manual?

Siemens Synco 700 Specifications

General IconGeneral
BrandSiemens
ModelSynco 700
CategoryController
LanguageEnglish

Related product manuals