28
Siemens Building Technologies Technologies / HVAC Products CE1B3131x2-en 74 319 0346 0 a 19.11.2004
Info pages boiler
To reach the Info pages:
1. Return to the start page by pressing the ESC button.
2. Press the INFO button.
3. Turn the OK knob until the required page appears.
Boilers 1…6
(Only with RMK770)
For each boiler installed in the plant, the display shows:
Actual value boiler temperature
This is the current boiler temperature.
Boiler temperature setpoint
This is the boiler temperature called for by the plant.
State
On = boiler on
Off = boiler off
Cause
Here, the reason for the boiler’s state is given.
Boiler
(Only with RMH760)
Actual value of the boiler temperature
This is the current boiler temperature.
Boiler temperature setpoint
This is the boiler temperature called for by the plant.
Return temperature
This is the temperature of the water returning to the
boiler from the consumers (heating circuit, DHW cir-
cuit).