k.4.1.1Checklistpriortostart‐up
Istheunitassembledcorrectlywithitsfunctionsinthecorrectorder?Seeannex2.
Arethesectionsandductsassembledcorrect?Seeannexi.
Checkthatfansandanti‐vibrationmountsarenotdamagedaftertransportationandinstallation.
Isthe
rotaryexchangerturningfreely?
Aresafetyguardsinstalledcorrectly?
Iftheunitincludesintegratedheatpump(DVU),checkwhetheritisinstalledandsupervisedby
qualifiedservicepersonnel.
IftheunitcontainsElectricairheater,makesurethatthesupplyisolatordisconnectswiththeunit.
Ducts‐are
allductsinstalled?
Externalcomponents‐arethevalveandvalvemotorinstalledcorrectly?
Isthecirculationpu mpinstalledcorrectly?
Iswaterunderpressureinthecoilandcirculationpump?
Arethepressuretransmittersinstalledandconnectedcorrectly?(Ifthisisasystemwithpressure
transmittersin
theducts)
Mainpowersupply:
o Connectedcorrectly?(3x400V+N+PE)
o Arecontrolsignalsforactuatorsconnectedcorrectly?
k.4.1.2Switchonpower
Donotstartuntilallsafetyprocedureshavebeencompletedandensurethatinspectiondoorsareclosed
andlocked.
Switchonpowerandthe
unitshouldbereadyforthestart‐up.
k.5Descriptionoffunctions
k.5.1Heatingcoilforhotwaterpreparedfortemperaturesensor(frostprotection)
FromSystemaireveryheatingcoilforhotwaterisprovidedwithalittlepipeatthecollectionpipeforthe
returnwater.Thislittlepipeispreparedfortheinstallationofatemperaturesensorforthetransmissionof
the
returnwatertemperaturetothecontroller.Thetemperaturesensorisnotincluded.
k.5.2DXcooling
CablesandflowguardarenotdeliveredbySystemair
k.5.3Circulationpump,heating
CirculationpumpisnotincludedinthedeliveryfromSystemair.
k.5.4Electricalheaterbattery
k.5.4.1Controlofheatingcapacityconnectedtounit
withoutSystemaircontrolsystem
Electricalheaterinstalledwithseparatecontrollerbesidetheheater.Theseparatecontrollerisdesignedfor
capacityconversionof0‐10Vcontrolsignalfromthemaincontrolsystem.Nopowersupplycablesare
connectedtotheelectricheater.Theseparatecontrollerfo rtheheateriswithoutsupply
disconnecting
device.