49
r.4.3.2Motorandbeltdrive
Thebearingsarefactorylubricatedanddonotrequireanyservicelubrication.Thebeltdriveistobe
checkedforcorrecttightnessandthatitisundamaged.OnsmallerAHU,therotorisfittedwithanelastic
beltdriveandsuppliedwithareservebelt
ontherotor.Thisbeltdrivedoesnotrequireserviceandcannot
beshortened.Anewbeltcanbefittedusingspecialisttools.OnlargerheatexchangerstherotorhasaV‐
beltwithabeltconnector.Ifthebeltisnolongertight,itmustbe shortenedtoa
lengthwhichenable sthe
motorbaseframetighteningspringtoholdthebelttight.Ifnewscrewsareusedforthebeltconnector,
theymustnothavealengthwhichexceedsthethicknessofthebeltandconnector.Removetheexcess,if
any,withafile.
r.4.4Crossflowand
counterflowexchanger
Onceayeartheedgesoftheheatexchangerplatesaretobechecked for
cleanliness
anddamage.
Ifthereisdustontheedgesofthe
pla
tes,removeitwithasoftbrush.Ifgreaseorothersuchsubstances
arepresent,thentheedgesmustbewashedusinggreasedissolvingdetergents
.
r.4.4.1By‐passdamper
Thedamperbladesarefittedwithsyntheticbearingsrequiringnolubrication.Eachdamperbladeis
connected byapivotingsystem.Thesteelrods andbrassbushesdo not requirelubrication.Air‐tightnessof
thedampers,whenthedampermotor isintheclosedposition,mustbe
visually
checkedonceayear.The
dampermotor istobeadjustedifthedamperdoesnot closetightly.
r.4.4.2Condensatewaterdrain
Onceayearcleanthedriptraybeneaththeheatexchanger,aswellasthedrainandthewater
trap.
Takecarethatthatthereissufficientwaterinthewatertrap.If adropleteliminatorhasbeenfitted,this
mustbe
checked
onceayearandcleanedifnecessary.