E6581581
- 1 -
Introduction
Thank you for purchasing the “EtherNet/IP™ option (IPE001Z)” for TOSVERT
VF-AS1/PS1 inverter. Before using EtherNet/IP™ option, carefully read this function
manual in order to completely and correctly utilize its excellent performance.
After reading this function manual, please keep it handy for future reference.
For details of its general handling, see an instruction manual attached with the option
unit.
- TOSVERT VF-AS1 Instruction Manual......................................E6581301
- TOSVERT VF-PS1 Instruction Manual......................................E6581386
- IPE001Z Instruction Manual ......................................................E6581580
EtherNet/IP™ is a trademark of ControlNet International, Ltd.
Handling in general
Warning
Prohibited
Do not connect or disconnect a network cable while the Inverter power is on.
It may lead to electric shocks or fire.
Mandatory
See the instruction manual attached with the option unit for cautions the handling.
Otherwise, it may lead to electric shocks, fire, injuries or damage to product.
Network control
Warning
Prohibited
Do not send the value out of the valid range to network variables.
Otherwise, the motor may suddenly start/stop and that may result in injuries.
Mandatory
Use an additional safety device with your system to prevent a serious accident due to the
network malfunctions. Usage without an additional safety device may cause an accident.
Caution
Mandatory
Set up “Communication error trip function (see below)” to stop the Inverter when the
option unit is deactivated by an unusual event such as tripping, an operating error,
power outage, failure, etc.
- Network Time-Out, Inverter operation at disconnection, Preset speed operation
selection
(Refer to “3.2.3 Network error detection (f849 - f852)”)
Deactivated
the option unit may cause an accident, if the “Communication error trip
function” is not properly set up.
Make sure that the operation signals are STOP before resetting Inverter’s fault. The
motor may suddenly start and that may result in injuries.
Notes on operation
Notes
When the control power is shut off by the instantaneous power failure, communication
will be unavailable for a while.
The Life of EEPROM is approximately 100,000 times. Avoid writing a command more
than 100,000 times to the same parameter of the Inverter and the communication board.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS1 Series and is the answer not in the manual?

Toshiba TOSVERT VF-AS1 Series Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-AS1 Series
CategoryInverter
LanguageEnglish

Related product manuals