EasyManuals Logo
Home>Toshiba>Inverter>TOSVERT VF-AS3

Toshiba TOSVERT VF-AS3 User Manual

Toshiba TOSVERT VF-AS3
622 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #215 background imageLoading...
Page #215 background image
E6582062ï‚‚
5-49 5. [Fundamental operation] How to use parameters
3
4
5
9
5. 3. 6 Increasing starting torque
<vb: Manual torque boost 1>
â–  Function
The starting torque is increased by increasing the setting value when starting torque is required. It is
valid when the setting value of <Pt: V/f Pattern> is "0: V/f constant", "1: Variable torque", or "7: V/f 5-
point setting".
â–  Parameter setting
â–  Reference of setting
100% is based on 200V, or 400V.
Set the value within +2% of the default setting, generally.
Title Parameter name Adjustment range Unit Default setting
vb Manual torque boost 1 0.00 - 30.00 %
*1
*1 Depending on the capacity. Refer to [11. 6].
Important
• The optimum value is programmed for each inverter capacity by default setting. When a value
larger than the reference value is set, an overcurrent trip may occur at startup.
• Repeated operation with excessive torque boost may cause failure of IGBT in the power circuit.
When larger stating torque is required, consider using vector control.
For details, refer to [5. 3. 4].
0.0HzSTOP
15:25
Min: 0.00 Max: 30.00
X1000 X100 X10 X1
%
vb :Manual torque boost 1
4.80
Basic parameter
00
Output frequency (Hz)
Output voltage (V)
<vLv: Base frequency voltage 1>
<vL: Base frequency 1>
<vb> (%)

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-AS3
CategoryInverter
LanguageEnglish

Related product manuals