5. 3. 6 Increasing starting torque
<vb: Manual torque boost 1>
â– Function
The starting torque is increased by increasing the setting value when starting torque is required. It is
valid when the setting value of <Pt: V/f Pattern> is "0: V/f constant", "1: Variable torque", or "7: V/f 5-
point setting".
â– Parameter setting
â– Reference of setting
100% is based on 200V, or 400V.
Set the value within +2% of the default setting, generally.
Title Parameter name Adjustment range Unit Default setting
vb Manual torque boost 1 0.00 - 30.00 %
*1
*1 Depending on the capacity. Refer to [11. 6].
Important
• The optimum value is programmed for each inverter capacity by default setting. When a value
larger than the reference value is set, an overcurrent trip may occur at startup.
• Repeated operation with excessive torque boost may cause failure of IGBT in the power circuit.
When larger stating torque is required, consider using vector control.
For details, refer to [5. 3. 4].
0.0HzSTOP
15:25
Min: 0.00 Max: 30.00
X1000 X100 X10 X1
%
vb :Manual torque boost 1
4.80
00
Output frequency (Hz)
Output voltage (V)
<vLv: Base frequency voltage 1>
<vL: Base frequency 1>
<vb> (%)