11-59 11. Table of parameters
1
3
9
10
11
The function No. in the following table can be assigned to parameters <F110>-<F124>, <F127>, <F128>.
and <F151>-<F158>.
11. 8 Input terminal function
Function number
Symbol Function Action
Reference
Positive
logic
Negative
logic
0 1 - No function Disabled -
23F Fwd run
ON: Forward run (except deceleration stop)
OFF: Deceleration stop
[7. 2. 1]
45R Rev run
ON: Reverse run (except deceleration stop)
OFF: Deceleration stop
6 7 ST Standby ON: Ready for operation, OFF: Coast stop (gate OFF)
[5. 4. 2]
[6. 3. 1]
[6. 34. 8]
[6. 8. 2]
[7. 2. 1]
8 9 RES1 Reset 1 ON: Acceptance of reset command, ON→OFF: Trip reset
[7. 2. 1]
[13. 1]
10 11 SS1 Preset speed switching 1
Selection of 31-speed SS1 to SS5 (5 bits)
[5. 3. 7]
[7. 2. 1]
12 13 SS2 Preset speed switching 2
14 15 SS3 Preset speed switching 3
16 17 SS4 Preset speed switching 4
18 19 JOG Jog run ON: Jog run enabled
[6. 10]
[7. 2. 1]
20 21 EXT Emergency off ON: "E" trip after <F603> operation
[6. 30. 4]
[7. 2. 1]
22 23 DB DC braking ON: DC braking
[6. 8. 1]
[6. 8. 3]
[7. 2. 1]
24 25 AD1 Acc/Dec switching 1
Selection of Acc/Dec 1 - 4 AD2, AD3 (2 bits)
[7. 2. 1]
26 27 AD2 Acc/Dec switching 2
28 29 VFSW1 V/f switching 1
Selection of V/f 1 - 4 VFSW1, VFSW2 (2 bits)
30 31 VFSW2 V/f switching 2
32 33 OCS2
Stall prevention
switching/Torque limit
switching 1
ON: <F185: Stall prevention level 2> enabled
OFF: <F601: Stall prevention level 1> enabled
[6. 24. 1]
[6. 27. 2]
[6. 30. 2]
[7. 2. 1]
Selection of Power running/Regenerative torque limit 1 - 4
OCS2, TRQL1 (2 bits)
34 35 TRQL2 Torque limit switching 2
[6. 24. 1]
[6. 27. 2]
[7. 2. 1]
36 37 PID PID control OFF ON: PID control OFF
[5. 3. 8]
[7. 2. 1]
38 39 PTTN1 Pattern operation 1 ON: Pattern operation 1 enabled
[6. 28]
[7. 2. 1]
40 41 PTTN2 Pattern operation 2 ON: Pattern operation 2 enabled
42 43 PTTNC
Pattern operation
continuation
ON: Pattern operation continued
44 45 PTTNS Pattern operation start ON: Pattern operation start
46 47 OH2 External thermal trip ON: "OH2" trip [7. 2. 1]

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-AS3
CategoryInverter
LanguageEnglish

Related product manuals