Page #288 background imageLoading...
Page #288 background image
E6582062ï‚‚
6. [Advanced] How to use parameters 6-46
4
4
6
9
<F270: Jump frequency 1>
<F271: Jump frequency 1 band>
<F272: Jump frequency 2>
<F273: Jump frequency 2 band>
<F274: Jump frequency 3>
<F275: Jump frequency 3 band>
â–  Function
When you want to avoid resonance caused by the natural frequency of the mechanical system to
run the inverter, the resonant frequency can be jumped.
This characteristic has hysteresis given to the jump frequency.
â–  Parameter setting
â–  Setting method
You can set three jump frequencies. To do that, avoid the overlap of the adjustment range of each
jump frequency.
The frequency does not jump during acceleration or deceleration.
6. 11 Jumping the frequency to avoid the
resonant frequency
Title Parameter name Adjustment range Unit Default setting
F270 Jump frequency 1 0.0 - FH Hz 0.0
F271 Jump frequency 1 band 0.0 - 30.0 Hz 0.0
F272 Jump frequency 2 0.0 - FH Hz 0.0
F273 Jump frequency 2 band 0.0 - 30.0 Hz 0.0
F274 Jump frequency 3 0.0 - FH Hz 0.0
F275 Jump frequency 3 band 0.0 - 30.0 Hz 0.0
0.0HzSTOP
13:12
F270 : Jump frequency 1
Min: 0.0 Max: 80.0
X1000 X100 X10 X1
0.0
Hz
Output frequency (Hz)
<F270: Jump frequency 1>
0
Frequency setting signal
<F271: Jump frequency 1 band>
<F273: Jump frequency 2 band>
<F275: Jump frequency 3 band>
<F272: Jump frequency 2>
<F274: Jump frequency 3>

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-AS3
CategoryInverter
LanguageEnglish

Related product manuals