E6582062ï‚‚
10. Selection and installation of peripheral devices 10-4
9
10
According to the table [10. 2. 1], select an appropriate wiring device depending on the voltage class and
capacity of the inverter.
10. 2. 1 Selection table of a wiring device
Select a wiring device depending on the inverter type and input current in the table next.
â– Wiring devices for HD rating
10. 2 Selection of a wiring device
Voltage
class
Applicable
motor (kW)
Inverter type-form Input current (A)
Rated current (A)
Molded-case circuit
breaker (MCCB)
Earth leakage circuit
breaker (ELCB)
Magnetic contactor
(MC)
3-phase
240 V
0.4 VFAS3- 2004P 1.7
3 20
0.75 2007P 3.3
5 20
1.5 2015P 6.0
10 20
2.2 2022P 9.0
15 20
4.0 2037P 15.1
20 20
5.5 2055P 20.1
30 32
7.5 2075P 27.3
40 32
11 2110P 40.0
50 50
15 2150P 53.2
75 60
18.5 2185P 64.8
100 80
22 2220P 78.3
100 80
30 2300P 104.7
150 150
37 2370P 128.4
175 200
45 2450P 157.6
200 260
55 2550P 189.0
250 260