6-69 6. [Advanced] How to use parameters
3
4
6
9
<F320: Droop gain>
<F321: Frequency at 0% droop gain>
<F322: Frequency at F320 droop gain>
<F323: Droop deadband torque>
<F324: Droop output filter>
â–  Function
Droop control is a function that prevents loads from concentrating at a specific motor due to load
imbalance when multiple inverters and motors are used to drive a common load.
These parameters are used to allow the motor to slip (drooping characteristic) according to the load
torque.
These parameters are used to adjust the frequency range, deadband torque, and gain.
â–  Parameter setting
â–  Setting methods
• Droop control is enabled when <Pt: V/f Pattern> is set to "3", "9", "10", or "11".
• When the applied torque is equal to or more than the deadband torque value, output frequency is
reduced during power running or increased during regeneration.
• Droop control is enabled at frequency range <F321: Frequency at 0% droop gain> or more.
• The amount of droop will vary depending on the output frequency for frequency ranges <F321:
Frequency at 0% droop gain> or more or <F322: Frequency at F320 droop gain> or less.
• For the frequency range over <vL: Base frequency 1>, the amount of error for <F323: Droop
deadband torque> will increase. Therefore, we recommend you use this parameter at base
frequency or less.
• Output frequency in droop control will not be limited by <FH: Maximum frequency>.
6. 16 Single load sharing by multiple inverters
(droop control)
Title Parameter name Adjustment range Unit Default setting
F320 Droop gain
0.0 - 100.0
*1
*1 Range that can be changed during run is 0.1 - 100.0%. Setting or changing to 0.0 (no droop) must be performed after stop.
%0.0
F321 Frequency at 0% droop
gain
0.0 - 320.0 Hz 10.0
F322 Frequency at F320 droop
gain
0.0 - 320.0 Hz 100.0
F323 Droop deadband torque 0 - 100 % 10
F324 Droop output filter 0.1 - 200.0 rad/s 100.0
0.0HzSTOP
13:20
F320 : Droop gain
Min: 0.0 Max: 100.0
X1000 X100 X10 X1
%
0.0

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-AS3
CategoryInverter
LanguageEnglish

Related product manuals