E6581611
K-7
11
Basic parameter 2
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0170 Base frequency 2 Hz 0.1/0.01 20.0-500.0 *1 6.8.1
0171 Base frequency
voltage 2
V 1/0.1 50-330 (240V class)
50-660 (500V class)
*1
0172 Torque boost
value 2
% 0.1/0.1 0.0-30.0 *2
0173 Motor electronic-
thermal protection
level 2
%
(A)
1/1 10-100 *12 100 5.6
6.8.1
6.29.1
0185 Stall prevention
level 2
%
(A)
1/1 10-199, *12
200 (disabled)
150 6.8.1
6.29.2
0190 V/f 5-point setting
VF1 frequency
Hz 0.1/0.01
0.0-fh
0.0 6.3
6.9
0191 V/f 5-point setting
VF1 voltage
%
(V)
0.1/0.1
0.0-125.0 *12
0.0
0192 V/f 5-point setting
VF2 frequency
Hz 0.1/0.01
0.0-fh
0.0
0193 V/f 5-point setting
VF2 voltage
%
(V)
0.1/0.1
0.0-125.0 *12
0.0
0194 V/f 5-point setting
VF3 frequency
Hz 0.1/0.01
0.0-fh
0.0
0195 V/f 5-point setting
VF3 voltage
%
(V)
0.10.1
0.0-125.0 *12
0.0
0196 V/f 5-point setting
VF4 frequency
Hz 0.1/0.01
0.0-fh
0.0
0197 V/f 5-point setting
VF4 voltage
%
(V)
0.1/0.1
0.0-125.0 *12
0.0
0198 V/f 5-point setting
VF5 frequency
Hz 0.1/0.01
0.0-fh
0.0
0199 V/f 5-point setting
VF5 voltage
%
(V)
0.1/0.1
0.0-125.0 *12
0.0
Frequency parameters
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0200 Frequency priority
selection
- - 0: (Switchable to by
terminal input)
0
5.8
6.10.1
1: (Switchable to at
1.0Hz or less of designated
frequency)
0201 VIA input point 1
setting
% 1/1 0-100 0
6.10.2
7.3
0202 VIA input point 1
frequency
Hz 0.1/0.01 0.0-500.0 0.0
0203 VIA input point 2
setting
% 1/1 0-100 100
0204 VIA input point 2
frequency
Hz 0.1/0.01 0.0-500.0 *1
0205 VIA input point 1
rate
% 1/0.01 0-250 0 6.31
0206 VIA input point 2
rate
% 1/0.01 0-250 100
0207 Frequency setting
mode selection 2
- - 0-14 (Same as ) 1
5.8
6.10.1
*1: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
*2: Default setting values vary depending on the capacity. Refer to section 11.4.
*12: When f701=1, adjustment range is 100%=rated current, or 100%=200V(240V class)/ 400V(500V class).