E6581611
E-5
5
5.3 Maximum frequency
: Maximum frequency
Function
1) Programs the range of frequencies output by the inverter (maximum output values).
2) This frequency is used as the reference for acceleration/deceleration time.
Output frequency
(Hz)
When 
=80Hz
When =60Hz
80Hz
60Hz
0 100% Frequency setting signal (%)
This function determines the value
in line with the ratings of the motor
and load.
Maximum frequency cannot be
adjusted during operation.To
adjust, first stop the inverter.
If  is increased, adjust the upper limit frequency  as necessary.
[Parameter setting]
Title Function Adjustment range Default setting

Maximum frequency 30.0-500.0 (Hz) 80.0