5.5 Base frequency
: Base frequency 1 : Base frequency voltage 1
Function
Set the base frequency and the base frequency voltage in conformance with load specifications or the
base frequency.
Note: This is an important parameter that determines the constant torque control area.
Output voltage [V]
Base frequency voltage
Output frequency (Hz)
0
[Parameter setting]
Title Function Adjustment range
Default setting
Base frequency 1 20.0-500.0 (Hz) 1
Base frequency voltage1
50-330 (240V class)
50-660 (500V class)
1
* 1: Default setting values vary depending on the setup menu setting. Refer to section 11.5.