28
SCXF-SVX01Q-EN
Steam and Hot Water Coils
Steam Coils
Figure 10. Steam Coil
Main Control Panel
Vacuum Trap Connection
Condensate Return
Vacuum Trap Connection
Steam Inlet Connection
Condensate Return
Air Inlet
L
K
F
N
M
H
J
A
C
B
Table 13. Piping locations for steam coils (in)(lbs)
Unit Size A B C D E F G H J K L M N
Weight
20-38 Ton
60-3/8 82-7/8
18 — —
22-3/8
— —
18-1/2 3-7/8
5
4-3/8 1-1/4
460
42-80 Ton
72-7/8 105-1/4
18 — —
13-1/4
— —
22-1/8 6-3/8
5-375
4-3/8 1-1/4
600
Note: Weight includes complete heating coil box.
Hot Water Coils
Figure 11. Hot Water Coil
Notes:
1. All coils are factory mounted, piped, and wired.
2. All piping connections are 1-1/2” (38.1mm) female NPT fittings.
Main Control Panel
Air Inlet
Hot Water Outlet Connection
Hot Water Inlet Connection
H
F
G
A
B
E
D
C
Table 14. Hot water coil piping locations & weight (in)(lbs)
Unit Size A B C D E F G H
Weight
20-38 Ton
60 3/8 82 7/8
18
20 5/8 8 1/8 22 3/8 3 5/8 8 1/4
460
42-80 Ton
72 7/8 105 1/4
18
24 1/2 10 3/4 13 1/4 3 5/8 8 1/4
600
Note: Weight includes complete heating coil box.