NNoottee:: Sufficient cooling load must be visible to
refrigerant circuit controls for mechanical
refrigeration to operate. If necessary,
temporarily reduce the discharge air setpoint
to verify the refrigeration cycle operation.
9. Check voltage at all compressor terminals to ensure
it is within 10% of nameplate voltage.
10. Check voltage imbalance from these three voltage
readings at each compressor. Maximum allowable
voltage imbalance, phase to phase is 2%.
11. Start the first step compressor only.
12. Check amp draw at compressor terminals. RLA and
LRA are on the unit nameplate.
13. Measure amp draw at evaporator fan motor
terminals. FLA data is on the motor nameplate.
14. As soon as a compressor starts, verify correct
rotation. If a scroll compressor is allowed to run
backwards for even a very short period of time,
internal compressor damage could occur and
compressor life could be reduced. When rotating
backwards scroll compressors make a loud noise,
do not pump, and draw about 1/2 expected amps,
and low side shell gets hot. Immediately shut off a
compressor rotating backwards and correct wiring.
NNOOTTIICCEE
CCoommpprreessssoorr DDaammaaggee!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn
ccoommpprreessssoorr ddaammaaggee..
IImmpprrooppeerr ppoowweerr pphhaassiinngg wwiillll ccaauussee ccoommpprreessssoorr ttoo
rruunn bbaacckkwwaarrddss.. CCoommpprreessssoorr ccoouulldd bbee rruunnnniinngg
bbaacckkwwaarrddss iiff iitt iiss nnooiissyy,, llooww ssiiddee sshheellll ggeettss hhoott,,
ssuuccttiioonn pprreessssuurree ddooeess nnoott ddrroopp wwiitthhiinn 55 sseeccoonnddss
aafftteerr ssttaarrttuupp,, aanndd ccoommpprreessssoorr oonnllyy ddrraawwss ½½
eexxppeecctteedd aammppss.. SSttoopp tthhee ccoommpprreessssoorr iimmmmeeddiiaatteellyy
aanndd hhaavvee aa qquuaalliiffiieedd eelleeccttrriicciiaann oorr tteecchhnniicciiaann
pprrooppeerrllyy ttrraaiinneedd iinn 33 pphhaassee ppoowweerr ccoorrrreecctt tthhee
wwiirriinngg..
15. AAiirr CCoooolleedd OOnnllyy: Check condenser fans for proper
rotation. From top of unit, correct rotation direction
is clockwise. If running backwards, correct wiring.
WWAARRNNIINNGG
RRoottaattiinngg CCoommppoonneennttss!!
FFaaiilluurree ttoo ddiissccoonnnneecctt ppoowweerr bbeeffoorree sseerrvviicciinngg ccoouulldd
rreessuulltt iinn rroottaattiinngg ccoommppoonneennttss ccuuttttiinngg aanndd ssllaasshhiinngg
tteecchhnniicciiaann wwhhiicchh ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss
iinnjjuurryy..
DDuurriinngg iinnssttaallllaattiioonn,, tteessttiinngg,, sseerrvviicciinngg aanndd
ttrroouubblleesshhoooottiinngg ooff tthhiiss pprroodduucctt iitt mmaayy bbee
nneecceessssaarryy ttoo wwoorrkk wwiitthh lliivvee aanndd eexxppoosseedd rroottaattiinngg
ccoommppoonneennttss.. HHaavvee aa qquuaalliiffiieedd oorr lliicceennsseedd sseerrvviiccee
iinnddiivviidduuaall wwhhoo hhaass bbeeeenn pprrooppeerrllyy ttrraaiinneedd iinn
hhaannddlliinngg eexxppoosseedd rroottaattiinngg ccoommppoonneennttss,, ppeerrffoorrmm
tthheessee ttaasskkss..
16. After 10 minutes, start second compressor of
manifold circuits.
17. Allow 10 minutes for circuit operation to stabilize at
full load.
18. Complete charging, if required.
Final Refrigerant Charge
If full charge was not used during installation, follow
these steps:
1. Determine remaining charge required by
subtracting charge added during “Preliminary
Refrigerant Charging,” p. 41 from the total.
2. With all circuit compressors running, SLOWLY
meter remaining R-410A into the suction line from
the LIQUID charging connection.
NNOOTTIICCEE
CCoommpprreessssoorr DDaammaaggee!!
OOvveerrcchhaarrggiinngg ssyysstteemm ccoouulldd rreessuulltt iinn ccoommpprreessssoorr
ffaaiilluurree aanndd//oorr rreedduucceedd ccoommpprreessssoorr lliiffee..
DDoo nnoott oovveerrcchhaarrggee ssyysstteemm.. EExxcceessssiivvee rreeffrriiggeerraanntt
cchhaarrggiinngg ccaann ccaauussee ccoommpprreessssoorr lliiqquuiidd sslluuggggiinngg aatt
ssttaarrttuupp,, aanndd ccoonnddiittiioonnss wwhheerree ccoommpprreessssoorrss aanndd//oorr
ccoonnddeennsseerr ffaannss sshhoorrtt ccyyccllee..
NNOOTTIICCEE
CCoommpprreessssoorr DDaammaaggee!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn
ccoommpprreessssoorr ffaaiilluurree aanndd//oorr rreedduucceedd ccoommpprreessssoorr
lliiffee..
TToo pprreevveenntt ccoommpprreessssoorr lliiqquuiidd sslluuggggiinngg,, oonnllyy aadddd
lliiqquuiidd iinn tthhee ssuuccttiioonn lliinnee wwhheenn tthhee ccoommpprreessssoorr iiss
rruunnnniinngg.. UUssee eexxttrreemmee ccaauuttiioonn ttoo mmeetteerr lliiqquuiidd
rreeffrriiggeerraanntt iinnttoo tthhee ssuuccttiioonn lliinnee sslloowwllyy.. IIff lliiqquuiidd iiss
aaddddeedd ttoooo rraappiiddllyy,, ccoommpprreessssoorr ooiill ddiilluuttiioonn aanndd ooiill
ppuummppoouutt ccoouulldd ooccccuurr..
3. Use an accurate scale to measure and record
amount of R-410A added.
4. After unit has been operating for approximately 30
minutes at full load, measure and record operating
pressures.
AAiirr CCoooolleedd OOnnllyy: Operating pressure measurement
must be made with all condenser fans running.
5. Repeat for other circuits.
6. Confirm, and adjust charge if needed, by checking
subooling at AHRI 340/360 full load operating
conditions (80/67°F entering evap, ~300CFM/ton, 85/
95°F EWT/LWT for water-cooled and 95°F OA for
air-cooled).
Water-cooled subcooling should be 8-10°F
Air-cooled subcooling should be 14-18°F
SSttaarrttuupp

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane IntelliPak SCWF 20 and is the answer not in the manual?

Trane IntelliPak SCWF 20 Specifications

General IconGeneral
BrandTrane
ModelIntelliPak SCWF 20
CategoryAir Conditioner
LanguageEnglish

Related product manuals