Tyco Electronics Galaxy SC Controller J85501F-1
Appendix B - 12 T1.317 Objects and Attributes Issue 13 February 2001
Table B-9: Battery Management Objects and Attributes, continued
Related Commands
ATTRIBUTE MNEM TYPE CHA OPE MET CON BACKUP VALUE
Slope Thermal Compensation STC
Identifier IDE TEXT SC1
Description DES TEXT X X X Slope Thermal Comp
State STT NUMBER X X X 0:disable 1:enable
Raise Voltage Enable RVE NUMBER X X X 0:disable 1:enable
Lower Temperature Threshold LTT NUMBER X X X -5-20 ×C or 23-68 ×F
Nominal Temperature Threshold NTT NUMBER X X X 15-30 ×C or 59-86 ×F
Upper Temperature Threshold UTT NUMBER X X X 30-55 ×C or 86-131 ×F
Step Temperature SPT NUMBER X X X 45-85 ×C or 113-185 ×F
Contactor CNT
Identifier IDE TEXT CN1, CN2, or CN3
Description DES TEXT X X X Contactor 1, 2, or 3
Status STT TEXT X NONE, DISCON, CONNECT,
FAILED
Type TYP TEXT X X X NONE, BATTERY, LOAD
Disconnect Threshold DTH NUMBER X X X 20-25:22V or 40-50:44V
Reconnect Threshold RTH NUMBER X X X 22-27:24V or 44-55:48V
Alarm Sub-Objects
Contactor Open Alarm CNO ATTRL CNO1, CNO2, or CNO3
Contactor Failed Alarm CNF ATTRL CNF1, CNF2, or CNF3