Tyco Electronics Galaxy SC Controller J85501F-1
Issue 13 February 2001 T1.317 Objects and Attributes Appendix B - 13
Table B-10: Alarm And Events Objects and Attribute
Related Commands
ATTRIBUTE MNEM TYPE CHA OPE MET CON BACKUP VALUE
System Alarms
Standard Alarm SDA
Identifier IDE TEXT see list below
Description DES TEXT X X X see below
Alarm State AST NUMBER 0:inactive 1:active
Severity SEV TEXT X X X CRIT MAJ, MIN, WRN, RO
LED LED TEXT X X X BATT, BD, DIST, RECT, AC,
RM, or CTLR
Contact Closure ACC TEXT X X X ACF, MJF, MNF, RFA, VLV, HV,
BD, CTLR, UR1, or UR2
Notify Delay DLY NUMBER X X X 0-540 seconds
Notify On Occur NOO NUMBER X X X 0:no 1:yes
Notify On Retire NOR NUMBER X X X 0:no 1:yes
NAG On Occur NAG NUMBER X X X 0:no 1:yes
Notify Destination DST TEXT X X X “”, P1,P2,P3,P4
IDE DEFAULT DESCRIPTION
CRA1 Controller Fail
CRF1 Controller Fuse
CPA1 Circuit Pack Fail
RPF1 Remote Peripheral Fuse
PCF1 PC Power Fuse
EPR1* External Password Reset
PFD1 Password At Default
EXL1* Excessive Login Attempts
BBL1 Memory Backup Battery Low
PHT1 Processor Halt
CLC1* Clock Changed
STF1* Self Test Failed
PGI1 Program Line Invalid
CCH1* Configuration Changed
HCL1* History Cleared
MOR1 Measurement Out Of Range
MTC1 Module Type Conflict
MDF1 Module Failure
BTJ1 Battery Thermal Major
BTN1 Battery Thermal Minor
AMJ1 Auxiliary Fuse Major
AMN1 Auxiliary Fuse Minor
FAJ1 External Fuse Major
FAN1 External Fuse Minor
RBF1 Regulation Battery Fuse
BTF1 Battery Thermal Fuse
BPF1 Battery Power Fuse
ABS1 Alarm Battery Supply
VSF1 Sense/Control Fuse
LVDA1 Low Voltage Disconnect Fail
LVD1 Low Voltage Disconnect
OSA1 Open String
EMD1 Energy Management Disabled
EPD1* Excess Plant Drain
SNC1 Shunt Not Configured
URC1 User Relay Conflict
ZID1 ID Not Configured
TPA1 Thermal Probe Failure
CMA1 Minor Communication Fail Alarm
MCM1 Major Communication Fail Alarm
BID1 Bay Interface ID Conflict
RFA1 Rectifier Fail
ACF1 AC Fail
PHA1 Phase Or Low Output
LCA1 Low Current
LSF1 Load Share Fuse
MAN1 Manual Off
ETS1 External Transfer Shutdown
RIC1 Rectifier Incomplete Config
HPA1 Half Power

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tyco Galaxy SC Controller and is the answer not in the manual?

Tyco Galaxy SC Controller Specifications

General IconGeneral
BrandTyco
ModelGalaxy SC Controller
CategoryController
LanguageEnglish

Related product manuals