Tyco Electronics Galaxy SC Controller J85501F-1
Appendix B - 14 T1.317 Objects and Attributes Issue 13 February 2001
Table B-10: Alarm And Events Objects and Attribute, continued
Related Commands
ATTRIBUTE MNEM TYPE CHA OPE MET CON BACKUP VALUE
IDE DEFAULT DESCRIPTION
DID1 ID Conflict
CLM1 Rectifier Current Limit
CFA1 Converter Fail
CFN1 Converter Fan Minor
CFJ1 Converter Fan Major
CDFA1 Converter Distribution Fuse
CDID1 Converter ID Conflict
COF1* Queue Overflow
COR1* Number Did Not Respond
NNC1 Number Not Configured
POR1* Number Did Not Respond
AAC1 ACO Active
ATA1 Alarm Test Active
ATF1* Alarm Test Failed
ATB1* Alarm Test Aborted
BTA1 Battery Test Active
BFA1 Battery Test Failed
BCA1 Battery Type Conflict
CNO1 Contactor 1 Open
CNO2 Contactor 2 Open
CNO3 Contactor 3 Open
CNF1 Contactor 1 Failed
CNF2 Contactor 2 Failed
CNF3 Contactor 3 Failed
* These alarms can be cleared using the CLE command
Threshold Alarm THA
Identifier IDE TEXT see list below
Description DES TEXT X X X see below Alarm State AST
NUMBER 0:inactive 1:active
Severity SEV TEXT X X X CRIT, MAJ, MIN, WRN, RO
Threshold THR NUMBER X X X number
LED LED TEXT X X X BATT, BD, DIST, RECT, AC,
RM, or CTLR
Contact Closure ACC TEXT X X X ACF,MJF,MNF,RFA,VLV,HV,
BD,CTLR,UR1, or UR2
Notify Delay DLY NUMBER X X X 0-540 seconds
Notify On Occur NOO NUMBER X X X 0:no 1:yes
Notify On Retire NOR NUMBER X X X 0:no 1:yes
NAG On Occur NAG NUMBER X X X 0:no 1:yes
Notify Destination DST TEXT X X X “”,P1,P2,P3,P4
IDE DEFAULT DESCRIPTION THRESHOLD RANGE
VLA1 Very Low Voltage 20-25.5:23V or 40-51:46V
MFA1 Multiple Rectifier Fail 2-24:2
LMR1* Limited Recharge 0.5-1.0:0.8
ERD1* Excess Rectifier Drain 1.0-2.0:1.18
ETO1 Engine Transfer Timeout 0-60:30 minutes
RPI1* Rectifier/Plant Inconsistency 1.0-2.0:1.05
RTL1 Reserve Time Low 0-100:2 hours
CMFA1 Multiple Converter Fail 2-8:2
* These alarms can be cleared using the CLE command
Dual Threshold Alarm DTA
Identifier IDE TEXT see list below
Description DES TEXT X X X see below
Alarm State AST NUMBER 0:inactive 1:active
Severity SEV TEXT X X X CRIT, MAJ, MIN, WRN, RO
Float Threshold FTH NUMBER X X X number
Boost Threshold BTH NUMBER X X X number
LED LED TEXT X X X BATT, BD, DIST, RECT, AC,
RM, or CTLR
Contact Closure ACC TEXT X X X ACF,MJF,MNF,RFA,VLV,HV,
BD,CTLR,UR1, or UR2
Notify Delay DLY NUMBER X X X 0-540 seconds
Notify On Occur NOO NUMBER X X X 0:no 1:yes
Notify On Retire NOR NUMBER X X X 0:no 1:yes
NAG On Occur NAG NUMBER X X X 0:no 1:yes