Tyco Electronics Galaxy SC Controller J85501F-1
Issue 13 February 2001 T1.317 Objects and Attributes Appendix B - 17
Table B-12: Remote Peripheral Monitor Objects and Attributes
Related Commands
ATTRIBUTE MNEM TYPE CHA OPE MET CON BACKUP VALUE
Remote Peripheral Monitor RPM
Identifier IDE TEXT Mxx (x=0-9,A-F, i.e. xx is 01 to FF)
Description DES TEXT X X X 30 char (type Module xx)
Serial Number SER NUMBER
Status STT TEXT ATTACHED,DETACHED, FAIL,
TYPE CONFLICT
Module Type TYP TEXT SHM, VTM, TPM
Type Lock TLK NUMBER X X X 0:not locked 1:locked
Measurement Out Of Range MOR NUMBER 0:inactive 1:active
Module Failure MDF NUMBER 0:inactive 1:active
Type Conflict MTC NUMBER 0:inactive 1:active
Voltage Monitor VTM
Identifier IDE TEXT Ccxx (x=0-9,A-F;c=1-6)
Description DES TEXT X X X 30 char (Voltage Chan c Module
xx)
Status STT TEXT ATTACHED,DETACHED, FAIL,
TYPE CONFLICT
Channel Type TYP TEXT VTM
Range RNG TEXT text
Value VAL NUMBER X number units
Unit UNI TEXT X X X 5 chars (default: V)
Offset OFS NUMBER X X X -99999-99999:0
Scale Factor SCF NUMBER X X X -99999-99999:1
Measurement Out Of Range MOR NUMBER 0:inactive 1:active
Shunt MonitorSHM
Identifier IDE TEXT Ccxx (x=0-9,A-F;c=1-6)
Description DES TEXT X X X 30 char (Shunt Chan c Module xx)
Status STT TEXT ATTACHED,DETACHED, FAIL,
TYPE CONFLICT
Channel Type TYP TEXT SHM
Range RNG TEXT text
Value VAL NUMBER X number A
Shunt Current SHA NUMBER X X X -2,147,483,648-2,147,483,648:1 A
Shunt Voltage SHV NUMBER X X X -2,147,483,648-2,147,483,648:
1mV (not 0)
Measurement Out Of Range MOR NUMBER 0:inactive 1:active
Temperature Monitor TPM
Identifier IDE TEXT Ccxx (x=0-9,A-F;c=1-7)
Description DES TEXT X X X 30 char (Temperature Chan c
Module xx)
Status STT TEXT ATTACHED,DETACHED,
FAIL,TYPE CONFLICT
Channel Type TYP TEXT TPM
Value VAL NUMBER X number C or F
Measurement Out Of Range MOR NUMBER 0:inactive 1:active
Control Relay CRM
Identifier IDE TEXT Ccxx (x=0-9,A-F;c=1-3)
Description DES TEXT X X X 30 char (Relay Chan c Module xx)
Status STT TEXT ATTACHED,DETACHED,
FAIL,TYPE CONFLICT
Channel Type TYP TEXT CRM
Value VAL NUMBER X X OFF or ON
Program Line PRG TEXT X X X 60 char (default: “”)
Measurement Out Of Range MOR NUMBER 0:inactive 1:active
Binary Monitor BIM
Identifier IDE TEXT Ccxx (x=0-9,A-F;c=1-6)
Description DES TEXT X X X 30 char (Binary Chan c Module xx)
Status STT TEXT ATTACHED,DETACHED,
FAIL,TYPE CONFLICT
Channel Type TYP TEXT BIM
Value VAL NUMBER X CLOSED or OPEN
Measurement Out Of Range MOR NUMBER 0:inactive 1:active
Derived Channels DRC
Identifier IDE TEXT DRnn (nn=01 to 32)
Description DES TEXT X X X 30 char (Derived Chan nn)
Value VAL NUMBER X number units
Program Line PRG TEXT X X X 60 char (default: “”)
Unit UNI TEXT X X X 5 chars (default: “”)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tyco Galaxy SC Controller and is the answer not in the manual?

Tyco Galaxy SC Controller Specifications

General IconGeneral
BrandTyco
ModelGalaxy SC Controller
CategoryController
LanguageEnglish

Related product manuals