Tyco Electronics Galaxy SC Controller J85501F-1
Issue 13 February 2001 T1.317 Objects and Attributes Appendix B - 17
Table B-12: Remote Peripheral Monitor Objects and Attributes
Related Commands
ATTRIBUTE MNEM TYPE CHA OPE MET CON BACKUP VALUE
Remote Peripheral Monitor RPM
Identifier IDE TEXT Mxx (x=0-9,A-F, i.e. xx is 01 to FF)
Description DES TEXT X X X 30 char (type Module xx)
Serial Number SER NUMBER
Status STT TEXT ATTACHED,DETACHED, FAIL,
TYPE CONFLICT
Module Type TYP TEXT SHM, VTM, TPM
Type Lock TLK NUMBER X X X 0:not locked 1:locked
Measurement Out Of Range MOR NUMBER 0:inactive 1:active
Module Failure MDF NUMBER 0:inactive 1:active
Type Conflict MTC NUMBER 0:inactive 1:active
Voltage Monitor VTM
Identifier IDE TEXT Ccxx (x=0-9,A-F;c=1-6)
Description DES TEXT X X X 30 char (Voltage Chan c Module
xx)
Status STT TEXT ATTACHED,DETACHED, FAIL,
TYPE CONFLICT
Channel Type TYP TEXT VTM
Range RNG TEXT text
Value VAL NUMBER X number units
Unit UNI TEXT X X X 5 chars (default: V)
Offset OFS NUMBER X X X -99999-99999:0
Scale Factor SCF NUMBER X X X -99999-99999:1
Measurement Out Of Range MOR NUMBER 0:inactive 1:active
Shunt MonitorSHM
Identifier IDE TEXT Ccxx (x=0-9,A-F;c=1-6)
Description DES TEXT X X X 30 char (Shunt Chan c Module xx)
Status STT TEXT ATTACHED,DETACHED, FAIL,
TYPE CONFLICT
Channel Type TYP TEXT SHM
Range RNG TEXT text
Value VAL NUMBER X number A
Shunt Current SHA NUMBER X X X -2,147,483,648-2,147,483,648:1 A
Shunt Voltage SHV NUMBER X X X -2,147,483,648-2,147,483,648:
1mV (not 0)
Measurement Out Of Range MOR NUMBER 0:inactive 1:active
Temperature Monitor TPM
Identifier IDE TEXT Ccxx (x=0-9,A-F;c=1-7)
Description DES TEXT X X X 30 char (Temperature Chan c
Module xx)
Status STT TEXT ATTACHED,DETACHED,
FAIL,TYPE CONFLICT
Channel Type TYP TEXT TPM
Value VAL NUMBER X number C or F
Measurement Out Of Range MOR NUMBER 0:inactive 1:active
Control Relay CRM
Identifier IDE TEXT Ccxx (x=0-9,A-F;c=1-3)
Description DES TEXT X X X 30 char (Relay Chan c Module xx)
Status STT TEXT ATTACHED,DETACHED,
FAIL,TYPE CONFLICT
Channel Type TYP TEXT CRM
Value VAL NUMBER X X OFF or ON
Program Line PRG TEXT X X X 60 char (default: “”)
Measurement Out Of Range MOR NUMBER 0:inactive 1:active
Binary Monitor BIM
Identifier IDE TEXT Ccxx (x=0-9,A-F;c=1-6)
Description DES TEXT X X X 30 char (Binary Chan c Module xx)
Status STT TEXT ATTACHED,DETACHED,
FAIL,TYPE CONFLICT
Channel Type TYP TEXT BIM
Value VAL NUMBER X CLOSED or OPEN
Measurement Out Of Range MOR NUMBER 0:inactive 1:active
Derived Channels DRC
Identifier IDE TEXT DRnn (nn=01 to 32)
Description DES TEXT X X X 30 char (Derived Chan nn)
Value VAL NUMBER X number units
Program Line PRG TEXT X X X 60 char (default: “”)
Unit UNI TEXT X X X 5 chars (default: “”)