Tyco Electronics Galaxy SC Controller J85501F-1
Appendix B - 16 T1.317 Objects and Attributes Issue 13 February 2001
Table B-11: Data Switch Objects and Attributes
Related Commands
ATTRIBUTE MNEM TYPE CHA OPE MET CON BACKUP VALUE
Data Switch DSW
Identifier IDE TEXT DS1,DS2,DS3,DS4
Description DES TEXT X X X Data Switch n
Connected Equipment ID CID TEXT X X X GALAXY,OMNI, ECS, MCS,
XCS, RAS (up to 6 char)
State STT NUMBER X IDLE, REPORTING, PASS-TH
RU, N/A
Reporting Enable REN NUMBER X X X 0:disable 1:enable
Connect Baudrate BDR NUMBER X X X 300,1200,2400,4800,9600,19200
Data Bits DBT NUMBER X X X 7,8
Parity PRY TEXT X X X O,E,N
Stop Bits SBT NUMBER X X X 1,2
Handshake HSH TEXT X X X NO,SW,HW
Monitor DSR Signal DSR NUMBER X X X 0:no 1:yes
Alarm Header Length HDR NUMBER X X X 0 to 100 lines
Attention Prompt APR TEXT X X X 12 char (default: \r\,\r)
Password PWD TEXT X X X 20 char (default: LINEAGE\r)
Alarms Command ACM TEXT X X X 30 char (default: ALMS\r)
Hang-up Command HUC TEXT X X X 20 char (default: BYE\r)
Connected Equip Alarm CEA ATTRL CEA1, CEA2, CEA3, or CEA4