Appendix C - 6 T1.317 Error Messages Issue 13 February 2001
Diagnostic
Messages
Table C-1 lists various Galaxy diagnostic messages.
Table C-1: Galaxy Diagnostic Messages
Number Message
500
Rect cable module type is unknown
501
Phase failure produced excess ripple causing output breaker to trip
502
Short on output filter capacitor
503
Alarm board in rectifier failed
504
One phase of the ac input failed or rectifier diodes may have failed,
triacs or inductors failed
505
Commercial ac has failed or alarm board in rectifier failed
506
MAN off; if not turned off, check ckt packs and associated wiring
507
Failure in current limit ckt or possible personnel intervention
508
Rect failed due to high voltage, circuit packs in rectifier failed
509
RFA present; fuses in rect blew or internal HV circuit was operated
510
Simulated RFA not generated
511
LCA present; check load share setup
512
LSF present; check load share fuse
513
Excess rect drain; current limit failed or
mis-adjusted
514
Possible controller rect board fail
515
Rect type and rect cable module inconsistent
516
STCB off; if not turned off, check rect circuit breaker
517
LCA present; check load share setup
518
Rect failed due to high voltage, circuit packs in rectifier failed
519
RFA present; fan blocked or failed

Table of Contents