Issue 13 February 2001 T1.317 Error Messages Appendix C - 7
520
RFA present; fuses in rect blew or internal HV circuit was operated
521
AC fail; if no loss of ac, check rectifier connections
522
Excess RCT Drain: Possible rectifier board failure
523
Circuit Breaker Alarm: Rect CB open or fuse blown
524
RFA Present: Check room temp, check rectifier ventilation
525
RFA Present: Fan failed of fan stopped by rect low voltage
526
Rectifier is not responding: Check rectifier and connections
527
TR from remote operator request
528
TR from efficiency algorithm
529
TR from circuit breaker failure
530
TR from loss of phase
531
TR from the engine present
532
TR from sequencing event
533
Low plant voltage overrides TR which turned on rectifier
534
Rectifier type should be configured
600
Plant voltage wiring reversed
601
Plant shunt wiring reversed
602
Independent controller down; no plant or rectifier data or control
603
BTP temperature over %s
604
BTP temperature over %s, or BTP thermistor failure
605
Break in BTI caused BTN
606
Battery is at low voltage of %s
607
Batt discharge at %s min(s)
Table C-1: Galaxy Diagnostic Messages
Number Message

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tyco Galaxy SC Controller and is the answer not in the manual?

Tyco Galaxy SC Controller Specifications

General IconGeneral
BrandTyco
ModelGalaxy SC Controller
CategoryController
LanguageEnglish

Related product manuals