5.6 System and output configuration
5.6.1 Parameter P2xx overview
With parameter P200 – P203 the installed application and valve type can be selected.
With parameter P204 – P206 the valve characteristics can be set.
With parameter P207 – P214 the fan configuration can be set.
Application mode:
2-pipe system: 0…3
4-pipe system: 4…6
0 = Heating only
1 = Cooling only
2 = 2-pipe manual heating or cooling
3 = 2-pipe auto heat/cool changeover
4 = 4-pipe manual heating or cooling
5 = 4-pipe auto heat/cool changeover
6 = 4-pipe Heating and cooling
7 = Floor heating system
8 = Chilled ceiling system
9 = Heated/chilled ceiling system
0 = OFF = Electric heater disabled
1 = ON = Electric heater enabled
Fan stop delay after electric heating
Valve type of heating/cooling system
Note: Changing this parameter
will change output wiring! See
Note1
0 = on/off valve
1 = 3-position valve (only for 2-pipe systems)
2 = Modulating valve 0-10V
3 = Modulating valve 2-10V
3-position valve running time
Minimum on time of valve for on/off
type
Minimum off time of valve for on/off
type
Number of fan speeds
Note: Changing this parameter
will change output wiring! See
Note1
1 = 1 fan speed (only DO1)
3 = 3 fan speeds
4 = Analog fan (AO1)
Minimum on time of each fan speed
Low fan speed switch on level
(Switch off level 15% lower or 0%)
Note: Ignored for on/off valve (and
electric heater), see chapter 5.8
Control settings
Medium fan speed switching point
(Switch off level 15% lower)
High fan speed switching point
(Switch off level 15% lower)
0 = OFF = Fan kick disabled
5…1500 = period in minutes
Minimum fan speed in auto mode
0 = Fan off
1 = Low speed (In analog fan mode, minimum fan
speed is at 20% of range: (P211-P209)*0.2+P209)
Minimum fan speed in manual mode
0 = Fan off
1 = Low speed
Number of fan speeds for analog fan.
(Used in manual fan mode only. In
auto mode, the fan is running
continuously variable between P209
and P211)
1 = One fan speed, Min = P209 and Max = P211
3 = 3 fan speeds, regularly distributed between
P209 and P211
6 = 6 fan speeds, regularly distributed between
P209 and P211
Note 1: P203 will change the output assignment. See application overview for wiring.
- P203 = 0/1: DO01 and DO02 are used as valve outputs, AO01 is used as the 0-10V fan output.
- P203 = 2/3: DO01 to DO03 are used as 3-stage fan outputs, AO01 and AO02 are used as valve outputs.