TRA-F22x-A
CONFIGURATION
Doc: 70-00-0958A V1.0, 20221102 © Vector Controls GmbH, Switzerland Page 17-34
Subject to change without notice www.vectorcontrols.com
VECTOR
5.6 System and output configuration
5.6.1 Parameter P2xx overview
With parameter P200 P203 the installed application and valve type can be selected.
With parameter P204 P206 the valve characteristics can be set.
With parameter P207 P214 the fan configuration can be set.
Par/
Addr
Description
Data type / value
Default
R/
W
P200
Application mode:
2-pipe system: 0…3
4-pipe system: 4…6
0 = Heating only
1 = Cooling only
2 = 2-pipe manual heating or cooling
3 = 2-pipe auto heat/cool changeover
4 = 4-pipe manual heating or cooling
5 = 4-pipe auto heat/cool changeover
6 = 4-pipe Heating and cooling
7 = Floor heating system
8 = Chilled ceiling system
9 = Heated/chilled ceiling system
0
R/
W
P201
Enable electric heater
0 = OFF = Electric heater disabled
1 = ON = Electric heater enabled
0 = OFF
R/
W
P202
Fan stop delay after electric heating
0…600 sec
60
R/
W
P203
Valve type of heating/cooling system
Note: Changing this parameter
will change output wiring! See
Note1
0 = on/off valve
1 = 3-position valve (only for 2-pipe systems)
2 = Modulating valve 0-10V
3 = Modulating valve 2-10V
2
R/
W
P204
3-position valve running time
20…500 sec
150 sec
R/
W
P205
Minimum on time of valve for on/off
type
1…30 min
1 min
R/
W
P206
Minimum off time of valve for on/off
type
1…30 min
1 min
R/
W
P207
Number of fan speeds
Note: Changing this parameter
will change output wiring! See
Note1
1 = 1 fan speed (only DO1)
3 = 3 fan speeds
4 = Analog fan (AO1)
3
R/
W
P208
Minimum on time of each fan speed
10…600 sec
120 sec
R/
W
P209
Low fan speed switch on level
(Switch off level 15% lower or 0%)
Note: Ignored for on/off valve (and
electric heater), see chapter 5.8
Control settings
0…25 %
10 %
R/
W
P210
Medium fan speed switching point
(Switch off level 15% lower)
30…75 %
60 %
R/
W
P211
High fan speed switching point
(Switch off level 15% lower)
80…100%
100 %
R/
W
P212
Fan kick period
0 = OFF = Fan kick disabled
5…1500 = period in minutes
0 = OFF
R/
W
P213
Minimum fan speed in auto mode
0 = Fan off
1 = Low speed (In analog fan mode, minimum fan
speed is at 20% of range: (P211-P209)*0.2+P209)
0
R/
W
P214
Minimum fan speed in manual mode
0 = Fan off
1 = Low speed
1
R/
W
P215
Number of fan speeds for analog fan.
(Used in manual fan mode only. In
auto mode, the fan is running
continuously variable between P209
and P211)
1 = One fan speed, Min = P209 and Max = P211
3 = 3 fan speeds, regularly distributed between
P209 and P211
6 = 6 fan speeds, regularly distributed between
P209 and P211
6
R/
W
Note 1: P203 will change the output assignment. See application overview for wiring.
- P203 = 0/1: DO01 and DO02 are used as valve outputs, AO01 is used as the 0-10V fan output.
- P203 = 2/3: DO01 to DO03 are used as 3-stage fan outputs, AO01 and AO02 are used as valve outputs.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vector TRA-F22 A Series and is the answer not in the manual?

Vector TRA-F22 A Series Specifications

General IconGeneral
BrandVector
ModelTRA-F22 A Series
CategoryController
LanguageEnglish

Related product manuals