TRA-F22x-A
CONFIGURATION
Doc: 70-00-0958A V1.0, 20221102 © Vector Controls GmbH, Switzerland Page 21-34
Subject to change without notice www.vectorcontrols.com
VECTOR
5.6.5 3-position valve control
The 3-position valve is controlled by DO1 and DO2. DO1 is used to open the valve while DO2 is used to close the valve.
When activating the 3-position valve, DO2 is on for two times the 3-position valve running time to ensure the valve is fully
closed.
5.6.6 Modulating valve control
The modulating valve is controlled by an analog output. There are two possible output ranges, 0-10V and 2-10V. The
different modulating valve types can be chosen with P203 (2 equals 0-10V, 3 leads to 2-10V).
5.6.7 Fan extension time for electric heater
When the electric heater is switched off, the fan keeps running for the time specified in P202 to avoid over-heating of the
electric heater.
The analog fan keeps running at 20% of range for the specified time.
5.6.8 Periodic fan kick
The periodic fan kick is disabled by default settings. The periodic fan kick is only available with a 3-stage fan (P207 = 3).
In automatic fan mode, if the fan speed is 0, the fan will be set to fan speed 1 periodically with the time defined with
P212. The fan runs after this period for the minimum on time for fan speeds (P208).
5.6.9 Floor heating system with or without floor temperature limitation
Detailed explanation of floor temperature limitation is given in chapter 5.9 Temperature and digital inputs, page 28.
The floor heating system can be configured with or without floor temperature limitation.
Parameter setting…
with floor temperature limitation
without floor temperature limitation
P200 (Application Mode)
7 = Floor heating system
7 = Floor heating system
P500/P502 (Input RT1/RT2
Configuration)
2 = Heat/cool changeover or floor
temperature sensor (NTC or DI)
Not 2 (0 - 1, 3 - 7)
P501/P503 (Definition of RT1/ RT2)
0 = NTC temperature sensor
X
P505 (Floor temperature limit)
Set limitation (Default: 30°C/86°F)
Ignored
3
2
1
0
Time
P208
Fan Speed
Fan in auto mode
P208
P212

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vector TRA-F22 A Series and is the answer not in the manual?

Vector TRA-F22 A Series Specifications

General IconGeneral
BrandVector
ModelTRA-F22 A Series
CategoryController
LanguageEnglish

Related product manuals