5.6.3 Application modes: Wiring diagrams of outputs
Valve type of heating/cooling system
Number of fan speeds for analog fan
P200, P201, P203,
P207, P215 settings
Wiring diagram of outputs
• 2-pipe system
• on/off valve
• DO1: Heating or cooling
• AO1: 0-10V analog Fan
Manual heating or cooling
Analog fan
Automatic heating or cooling
Analog fan
6 = 6 fan speeds (in
manual fan mode)
• 2-pipe system
• Modulating valve
• Heating or cooling
• AO1: 0-10V modulating
valve
• DO1-3: 3 stage fan
2 = 0-10V Modulating
valve
Manual heating or cooling
3-stage fan
Automatic heating or cooling
3-stage fan
• 2-pipe system cooling
only with electric heater
• on/off cooling valve
• DO1: Cooling
• DO2: Electric Heater
• AO1: 0-10V analog Fan
Cooling with electric heater
Analog fan
1 = ON = Electric
heater enabled
6 = 6 fan speeds (in
manual fan mode)
• 4 pipe system
• on/off valve
• Heating and/or cooling
• DO1: Cooling
• DO2: Heating
• AO1: 0-10V analog Fan
Manual heating or cooling
3-stage fan
Auto heating or cooling
RT1 as normally open DI
3-stage fan
Heating and cooling
3-stage fan
6 = 6 fan speeds (in
manual fan mode)
• Floor heating system
• on/off valve
• DO1: Heating
Floor heating
On/off valve
Heated/Chilled ceiling
On/off valve