TRA-F22x-A
GENERAL DESCRIPTION
Doc: 70-00-0958A V1.0, 20221102 © Vector Controls GmbH, Switzerland Page 2-34
Subject to change without notice www.vectorcontrols.com
VECTOR
1 General Description
The TRA-F22x-A is a communicating electronic fan coil controller that controls the room temperature.
It supports motorized valves in 2-pipe and 4-pipe fan coil units (heating or cooling). There is an analog or digital
fan available. The digital fan supports 1- or 3 fan speeds, whereas the analog fan runs continuously variable.
Additional inputs can be used for external temperature sensor, room occupancy (motion) detection and more.
The controller offers the operating modes Comfort, Economy and Protection.
The TRA-F221-A includes a Modbus RTU interface and can easily be integrated into a building automation system.
Typical application includes:
Fan coil systems
- 2-pipe fan coil (cooling or heating on/off valve)
- 2-pipe fan coil (cooling or heating modulating valve)
- 2-pipe fan coil with 3-position valve (cooling or heating valve)
- 2-pipe fan coil and electric heater
- 4-pipe fan coil (cooling and heating on/off valve)
- 4-pipe fan coil (cooling and heating modulating valve)
Floor heating systems (on/off, modulating or 3-position valve)
Chilled/Heated ceilings or chilled beams systems (on/off, modulating or 3-position valve)
1.1 Features
LCD display with backlight
Room temperature control via built-in temperature sensor
2 configurable inputs temperature or digital
2 analog outputs for modulating valve control or analog fan
3 digital outputs for 1- or 3-speed fan control or digital valves (on/off or 3-position valve)
Comfort, Economy and Protection operating mode
Display of current room temperature or temperature set point in °C or °F
Display of outdoor temperature received from Modbus master
Manual or automatic heating / cooling changeover
Select operating mode via operating mode button on the controller
Minimum and maximum limitation of room temperature set point
Floor heating temperature limitation
Key lock function
RTU Modbus slave interface (TRA-F221 only)
Reload default settings for commissioning and control parameters
110230 VAC operating voltage
Flush mount on all 75x75x35mm wall mounting box or larger boxes
Selection of application via parameter
No data loos on power fail
1.2 Safety
DANGER! Safety advice
This device is for use as an operating controller. It is not a safety device. Where a device failure could endanger
human life and property, it is the responsibility of the client, installer and system designer to add additional safety
devices to prevent such a device failure. Ignoring specifications and local regulations may cause equipment
damage and endangers life and property. Tampering with the device and misapplication will void the warranty.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vector TRA-F22 A Series and is the answer not in the manual?

Vector TRA-F22 A Series Specifications

General IconGeneral
BrandVector
ModelTRA-F22 A Series
CategoryController
LanguageEnglish

Related product manuals