Programming Premium Unit
10
2.3 Programming level 3 at 15 °C, Premium Card TECC 4.25
Display Setting Default Min Max Unit
0 Cut-out value for low voltage 195 160 210 Volt
1 Remote control activated/deactivated 0 0 1
2 Choice of small relay setting indicating heat/cool cycle
0 = C1 + T1 closed at heat cycle (F4, F5).
C1 + R1 closed at cool cycle (F1, F3, F4).
C1 + R1 closed at system block.
00 Chiller
1 = For fault messages, system block (A01, A02, A09 etc.)
C1 + R1 closed, no faults.
C1 + T1 closed, system block/ failures.
001
0 for C5
3 Choice of thermostatic regulation or permanent ventilation 0 0 1
4 Choice of internal/external air temperature sensor 0 0 1
5 Choice of temperature reading in °C or °F 0 0 1
6 Calibration of blower speed 5 70 1 70
7 Calibration of blower speed 4 40 1 70
8 Calibration of blower speed 3 35 1 70
9 Calibration of blower speed 2 29 1 70
A Calibration of blower speed 1 23 1 70
b Access code for programming levels 0 0 99
C Duration of heat cycle in dehumidification mode 1 1 99 minutes
D Duration of cool cycle in dehumidification mode 1 1 99 minutes
E Delay before first start 1 1 20 seconds