Programming Cabin Controls
13
4 Programming Cabin Controls
4.1 Cabin Card 6.25
4.1.1 Setting
4.1.2 Programming level 3 at 29 °C, Cabin Card 6.25
4.1.3 Programming level 3 at 15 °C, Cabin Card 6.25
Display Setting Default Min Max Unit
b Selection of blower speed A 0 A
H Water temperature
F Selection of function mode 1 1 3
d Dehumidification cycle when system turned off (0 = non ac-
tive; 1 = 1 cycle per 24h; 2 = 2 cycles per 24h ; 3 = 3 cycles per
24h)
003
t Time to display table F 1 1 5 20 sec.
Display Setting Default Min Max Unit
4 Calibration chilled water temperature 0 -55 55 1/10°
5 Time for display standby 15 5 99 seconds
6 Time delay for first start 5 1 20
7 Calibration of air temperature 0 -55 55 1/10°
b Program version v6.2*
Display Setting Default Min Max Unit
1 Remote control activated/deactivated 0 0 1
2 Choice of blower type 1 0 2
3 Choice of thermostatic regulation or permanent ventilation 0 0 1
4 Choice of internal/external air temperature sensor 0 0 1
5 Choice of temperature reading in °C or °F
0 = °C, 1 = °F
001
6 Calibration of blower speed 5 70 1 70
7 Calibration of blower speed 4 40 1 70
8 Calibration of blower speed 3 35 1 70
9 Calibration of blower speed 2 29 1 70
A Calibration of blower speed 1 23 1 70
b Access code for programming levels 0 0 99
C Duration of heat cycle in dehumidification mode 1 1 99 minutes
D Duration of cool cycle in dehumidification mode 1 1 99 minutes