Programming Premium Unit
9
2.2 Programming level 3 at 29 °C, Premium Card TECC 4.25
Display Setting Default Min Max Unit
0 Lower cut-out value in cool mode for chilled water tempera-
ture outlet
4015°
1 Cut-in value in cool mode for chilled water temperature outlet 7 2 18 °
2 Higher cut-out value in heat mode for chilled water tempera-
ture outlet
40 30 49 °
3 Cut-in value in heat mode for chilled water temperature outlet 37 27 52 °
4 Calibration chilled water temperature 0 -55 55 1/10°
5 Time for display standby 15 5 99 minutes
6 Calibration of chilled water temperature inlet 0 -55 55 1/10°
7 Calibration of air temperature 0 -55 55 1/10°
8 Calibration of voltage under 50 Hz 0 -30 50
9 Select function of relais 0 0 3
Operating as staging relay 0
Controlling 3 way valve air handler by TECC card 1
Alarm indication 2
Cycle indication 3 *
A Calibration of voltage under 60 Hz -10 -30 50
b Program Version 4.2*
c Lower cut-out value in cool mode for chilled water tempera-
ture inlet
6015°
d Cut-in value in cool mode for chilled water temperature inlet 9 2 18 °
E Higher cut-out value in heat mode for chilled water tempera-
ture inlet
40 30 49 °
F Cut-in value in heat mode for chilled water temperature inlet 37 27 52 °
* Water heater integration.