122
YORK INTERNATIONAL
YORK INTERNATIONAL CORPORATION
MILLENNIUM
SCREW CHILLER
UNIT STATUS
2:04PM 10 OCT 99
SYS 1 NO COOLING LOAD
SYS 2 COMPRESSOR RUNNING
OPTIONS
CHILLED LIQUID WATER
AMBIENT CONTROL STANDARD
REFRIGERANT TYPE R-22
PROGRAM VALUES
DSCH PRESS CUTOUT 399 PSIG
DSCH PRESS UNLOAD 375 PSIG
SUCT PRESS CUTOUT 44 PSIG
HIGH AMBIENT CUTOUT 130.0 ºF
LOW AMBIENT CUTOUT 25.0 ºF
LEAVING LIQUID CUTOUT 36.0 ºF
MOTOR CURRENT UNLOAD 100 %FLA
ANTI RECYCLE TIME 600 SECS
LOCAL/REMOTE MODE REMOTE
LEAD/LAG CONTROL AUTOMATIC
UNIT DATA
LEAVING LIQUID TEMP 49.0 ºF
RETURN LIQUID TEMP 58.2 ºF
MIXED LIQUID TEMP 51.3 ºF
COOLING RANGE 42.0 +/- 2.0 ºF
AMBIENT AIR TEMP 74.8 ºF
LEAD SYSTEM SYS 2
EVAPORATOR PUMP ON
EVAPORATOR HEATER OFF
ACTIVE REMOTE CONTROL NONE
SOFTWARE VERSION C.ACS.09.00
SYSTEM 1 DATA
COMPRESSORS STATUS OFF
RUN TIME 0- 0- 0- 0 D-H-M-S
MOTOR CURRENT 0 AMPS 0 %FLA
SUCTION PRESSURE 125 PSIG
DISCHARGE PRESSURE 131 PSIG
OIL PRESSURE 130 PSIG
SUCTION TEMPERATURE 68.4 ºF
DISCHARGE TEMPERATURE 68.8 ºF
OIL TEMPERATURE 68.8 ºF
SAT SUCTION TEMP 71.8 ºF
SUCTION SUPERHEAT 3.4 ºF
SAT DISCHARGE TEMP 74.5 ºF
DISCHARGE SUPERHEAT 6.3 ºF
SLIDE VALVE STEP 0
COOLER INLET REFRIG 44.6 ºF
LIQUID LINE SOLENOID OFF
ECONOMIZER TXV SOLENOID OFF
CONDENSER FAN STAGE OFF
COMPRESSOR HEATER ON
WYE-DELTA RELAY OFF
SYSTEM 2 DATA
COMPRESSORS STATUS ON
RUN TIME 0- 0-15-26 D-H-M-S
MOTOR CURRENT 104 AMPS 87 %FLA
SUCTION PRESSURE 57 PSIG
DISCHARGE PRESSURE 233 PSIG
OIL PRESSURE 218 PSIG
SUCTION TEMPERATURE 42.9 ºF
DISCHARGE TEMPERATURE 145.5 ºF
OIL TEMPERATURE 102.8 ºF
SAT SUCTION TEMP 31.7 ºF
SUCTION SUPERHEAT 11.2 ºF
SAT DISCHARGE TEMP 112.1 ºF
DISCHARGE SUPERHEAT 33.4 ºF
SLIDE VALVE STEP 70
COOLER INLET REFRIG 23.6 ºF
LIQUID LINE SOLENOID ON
ECONOMIZER TXV SOLENOID ON
CONDENSER FAN STAGE 3
COMPRESSOR HEATER OFF
WYE-DELTA RELAY ON
DAILY SCHEDULE
S M T W T F S * = HOLIDAY
MON START=00:00AM STOP=00:00AM
TUE START=00:00AM STOP=00:00AM
WED START=00:00AM STOP=00:00AM
THU START=00:00AM STOP=00:00AM
FRI START=00:00AM STOP=00:00AM
SAT START=00:00AM STOP=00:00AM
HOL START=00:00AM STOP=00:00AM
The Local and System Data display messages for the
YCAS 3-System models follow the same format as the
YCAS 2-System Model messages as given in the pre-
ceding paragraphs. The only difference is that after the
System 2 data is completed, pressing the key displays
System 3 data before looping back to the Load/Unload
Timer Display.
YCAS 4-System Models:
YCAS 4-System models are constructed in two sec-
tions. One section contains number 1 and 2 refrigerant
systems plus their associated evaporator. The second
section contains the number 3 and 4 refrigerant sys-
tems plus their associated evaporator. Both sections have
their own control panel, but only the System 1 and 2
panel is fitted with a keypad and display.
The Local and System Data display messages for the
YCAS 4-System models follow the same format as the
YCAS 2-system model messages as given in the pre-
ceding paragraphs. The only difference is that after the
System 2 Data is completed, pressing the
áá
áá
á key dis-
plays System 3 and System 4 data before looping back
to the Load/Unload Timer Display.
4.4 OPERATING DATA - REMOTE PRINTOUT
The follow text shows a typical example printout ob-
tained by pressing the Operating Data key with an op-
tional printer attached. In this case an example is shown
for a YCAS 2-system Chiller. YCAS 3-system models
and YCAS 4-system models provide similar printouts
for the appropriate number of systems:
The System Cooler Inlet Refrigerant
Temperature will be printed if the unit
is in R-407C mode.
Micropanel

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York MILLENNIUM YCAS0623 and is the answer not in the manual?

York MILLENNIUM YCAS0623 Specifications

General IconGeneral
BrandYork
ModelMILLENNIUM YCAS0623
CategoryChiller
LanguageEnglish

Related product manuals