48
YORK INTERNATIONAL
OPTIONAL SINGLE POINT POWER SUPPLY CONNECTION TO FACTORY CIRCUIT BREAKER
(One Field Provided Power Supply Circuit to the chiller. Field Connection to Circuit Breaker in Option Panel.
No internal Branch Circuit Protection per Motor Control Center

.)
CONTROL POWER SUPPLY (UNITS WITHOUT STANDARD CONTROL CIRCUIT TRANSFORMERS)
NO. OF
CONTROL MCA MAX DUAL NON-FUSED
COMPRESSORS
POWER (MAX LOAD ELEMENT DISCONNECT
SUPPLY CURRENT) FUSE SIZE SWITCH SIZE
2 115V-1Ø 20A 20A 30A
3 or 4
115V-1Ø 30A 30A 30A
(Non-CE 50/60Hz)
3 or 4
115V-1Ø 25A 30A 30A
(CE 50Hz)
ELECTRICAL DATA
COMPRESSOR DATA
MAXIMUM KW AND AMPERAGE VALUES FOR DXST COMPRESSORS
COMPRESSOR MODEL AND VOLTAGE CODE
DXS45LA - MOTOR CODE A DXS36LA - MOTOR CODE A DXS24LA - MOTOR CODE (TBD)
(B5N, B5E, B6N, B6E) (A5N, A5E, A6N, A6E) (C5N, C5E, C6N, C6E)
VOLTAGE CODE -17 -28 -40 -46 -50 -58 -17 -28 -40 -46 -50 -58 -17 -28 -40 -46 -50 -58
MAX KW 150 150 150 150 113 150 150 150 150 150 113 150 105 105 105 105 80 105
MAX AMPS 492 428 259 214 193 171 492 428 259 214 193 171 338 294 178 147 135 118
FAN DATA
FAN TYPE
NOMINAL POWER FULL LOAD AMPS LOCKED ROTOR AMPS
(kW) (FLA) (LRA)
STANDARD 1, 57 4, 4 18, 0
HIGH PRESSURE 3, 7 6, 8 46, 3
Option not available for units with CE Mark.
Field Supplied Wiring System #1 System #2
Model
Volts
MCA
1
Factory Supplied Breaker Compressor Fans
11, 12
Compressor Fans
11, 12
YCAS
Rating
2
Wire Range
7
(Lugs) RLA X-LRA Qty FLA(ea) LRA(ea) RLA X-LRA Qty FLA(ea) LRA(ea)
0373 380 269 400 (2) 3/0-250 107.9 761 3 4.4 17.1 107.9 761 3 4.4 17.1
0403 380 291 450 (2) 3/0-250 117.7 761 3 4.4 17.1 117.7 761 3 4.4 17.1
0453 380 340 500 (2) 3/0-250 139.5 979 3 4.4 17.1 139.5 979 3 4.4 17.1
0503 380 389 600 (3) 2/0-400 161.3 979 3 4.4 17.1 161.3 979 3 4.4 17.1
0543 380 352 500 (2) 3/0-250 140.6 979 4 4.4 17.1 140.6 979 4 4.4 17.1
0573 380 413 600 (3) 2/0-400 167.9 979 4 4.4 17.1 167.9 979 4 4.4 17.1
0623 380 447 700 (3) 2/0-400 183.1 979 4 4.4 17.1 183.1 979 4 4.4 17.1
0653 380 422 600 (3) 2/0-400 167.9 979 5 4.4 17.1 167.9 979 5 4.4 17.1
Technical Data

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York MILLENNIUM YCAS0623 and is the answer not in the manual?

York MILLENNIUM YCAS0623 Specifications

General IconGeneral
BrandYork
ModelMILLENNIUM YCAS0623
CategoryChiller
LanguageEnglish

Related product manuals